5.7.4.
Additional Directives
4
Please refer to the manufacturer’s instructions for the material in
question when installing the flue gas discharge and air supply
materials. If the flue gas discharge and air supply materials are not
installed according to the instructions (e.g. they are not leakproof,
not clamped in place etc.), this may cause hazardous situations
and/or result in bodily injury.
4
It must be possible to inspect the flue or chimney.
Please contact us for further information.
5.7.5.
Connection of the combustion gas exhaust
pipe
S
Insertion depth 30 mm
Mounting
Fit together the combustion gas exhaust pipes, without welding.
CAUTION
4
The flue gas discharge pipe must be smooth and
deburred.
4
Do not rest the pipes on the boiler.
4
Take in account the insertion depth of 30 mm when
measuring the length of pipe prior to cutting.
4
The pipes must allow no leakage of flue gases and be
resistant to corrosion.
4
Connect the pipes together without stress between
the sections.
4
The horizontal sections need to be constructed with a
gradient of 50 mm per metre: Back to the boiler.
5.8
Electrical connections
5.8.1.
Control unit
The boiler is not line- and neutral sensitive. The control unit is fully
integrated with the fan, venturi and gas block. The boiler is fully pre-
wired. The PCB has a connection to the connection box with
instrument panel, via the
HMI
connector. The PCB has a
RS232
connection for a PC/laptop via the
RS232
connector. The main
characteristics of the control unit are described in the table below.
Power supply voltage
230 VAC/50Hz
Fuse rating F1 (230 VAC) 1,6 AT
R000437-A
S
60/100mm
5. Installation
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
32
02092014 - 7619497-02