6.4.3.
Setting the air/gas ratio
1. Unscrew the plug of the flue gas measurement point.
2. Insert the probe for the flue gas analyser into the measurement
opening.
WARNING
Ensure that the opening around the sensor is completely
sealed when taking measurements.
CAUTION
The flue gas analyser must have a minimum accuracy of
±0.25% CO
2
.
n
Set the boiler to full load
1. Continue pressing for around 3 seconds on the
B
key. The status
signal for the
B
button is orange and always flashes green
briefly; Part load is set.
2. Press the
B
button again 2 times. The status signal for the
B
button is orange and always goes off briefly 2 times; Full load is
set.
4
The full load status can only be reached via the part
load status.
4
See drawing for the position of control screw
A
for full
load.
3. Set the percentage CO
2
for the gas type being used to the nominal
value. This should always be inside the highest and lowest setting
limit.
4
If the percentage CO
2
is too low, turn the screw
A
anticlockwise for a higher percentage.
4
If the percentage CO
2
is too high, turn the screw
A
clockwise for a lower percentage.
Full load CO
2
must be between 9.15 and 9.50 %.
n
Set the boiler to part load
1. Continue pressing for around 3 seconds on the
B
key. The status
signal for the
B
button is orange and always flashes green
briefly; The low speed mode is parameterised.
See drawing for the position of control screw
B
for part load.
T003127-B
R000592-B
A
B
R000591-B
A
B
B
6. Commissioning
Baxi MainEco Combi and System 24 - 28 - 35 / 18 - 24
48