Installation & Operating Instructions
BAPI-Stat 4 “X-Combo”, Room %RH and Temp. Sensor
BA/BS4XC
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com
Specifications subject to change without notice.
rev. 10/28/16
27939_ins_BS4XC
6 of 8
MODE MENUS Continued....
P5 - %RH Span Low Limit
:
(Factory set per order)
Move the UP/Down arrows in 1% increments between 0% to 100% span.
P6 - %RH Span High Limit: (Factory set per order)
Move the UP/Down arrows in 1% increments between 0% to 100% span.
P7 - Fixed Temperature Setpoint
(Must be within the Temperature spans set in menu page P3 and P4.)
This function is used for Temperature Setpoint Lockout Only. Move the UP/Down arrows in 1˚ increments
between -40 to 140 span. (˚F or ˚C must be selected first on Jumper J50.)
P8 - Temperature Setpoint Span Low Limit
(Must be within the Temp spans set in menu page P3 and P4.)
Move the UP/Down arrows in 1˚ increments between -40 to 140 span. (˚F or ˚C must be selected first on
Jumper J50.)
P9 - Temperature Setpoint Span High Limit
(Must be within the Temp spans set in menu page P3 and P4.)
Move the UP/Down arrows in 1˚ increments between -40 to 140 span. (˚F or ˚C must be selected first on
Jumper J50.)
P10 - %RH Setpoint
(Must be within the RH spans set in menu page P5 and P6.)
This function is used for %RH Setpoint Lockout Only. Move the UP/Down arrows in 1% increments between 0%
to 100% span.
P11 - %RH Setpoint Span Low Limit
(Must be within the RH spans set in menu page P5 and P6.)
Move the UP/Down arrows in 1% increments between 0% to 100% span.
P12 - %RH Setpoint Span High Limit
(Must be within the RH spans set in menu page P5 and P6.)
Move the UP/Down arrows in 1% increments between 0% to 100% span.
P13 - Temperature Offset
Move the UP/Down arrows in 0.1˚ increments between -5 to +5 ˚F or °C. This affects both the display and signal
output values.
P14 - %RH Offset
Move the UP/Down arrows in 0.1% increments between -5% to +5%. This affects both the display and the
signal output values.
P15 - Test & Balance Channel 1:
This only applies to the active Ch. 1 output. The passive sensor must use the (-TB) option and a board
mounted 3 position switch.
Move the UP/Down arrows to “+1” to output a high temp output. Move the UP/Down arrows to “0” to output
the normal temp value on the output. Move the UP/Down arrows to “-1” to output a low temp output. On exit
from programming mode, the active Test & Balance will no longer be active, so the output changes to the live
variable.
P16 - Setpoint Lockout
(Move the UP/Down arrows to change the lockout mode desired.)
00 = No Setpoint Lockout (Default)
01 = Temperature Setpoint Lockout Only. (See P7 for lockout value)
02 = Temperature Setpoint Lockout and %RH Setpoint Lockout. (See P7 and P10 for lockout value)
03 = %RH Setpoint Lockout Only. (See P10 for lockout value)
P17 - Temperature Display Resolution
(Move the UP/Down arrows to change the resolution to the desired value.)
01 = .1 Degree Temperature Resolution
02 = .5 Degree Temperature Resolution (Default)
03 = 1 Degree Temperature Resolution
Optional Technician Adjustments continued....