Overview and Identification

Fig. 1:

 BAPI-Stat 4 

X-Combo Dimensions

The BAPI-Stat 4 “X-Combo” (BA/BS4XC) Room Unit features 4 output channels and optional local indication of 

temperature and humidity. Additional options include Temperature Setpoint, Humidity Setpoint and Local Override. 

The optional LCD shows room temperature in °C or °F and room humidity in %RH. In addition, the unit has adjustable 

offsets for both temperature and humidity and is capable of having the range for 

the temp., humidity and setpoints changed in the field. 
The unit has 4 output channels. Channel 1 and 2 can be ordered as voltage 

or current, channel 3 as voltage or resistance and channel 4 as a passive 

temperature sensor or isolated override contact. 

Fig. 2:

 Unit with 

Override but No 

Display or Setpoint

Fig. 3:

 Unit with 

Override and Display 

but No Setpoint

Fig. 4:

 Unit with 

Override, Display 

and Setpoint

Mounting

JUNCTION BOX

1.  Pull the wire through the wall and out the junction box, leaving about six 

inches free. Pull the wire through the hole in the base plate.

2.  Secure the base to the box using the #6-32 x 5/8 inch mounting screws 

provided.

3.  Terminate the unit according to the guidelines in the 

Termination 

section.

4.  Attach Cover by latching it to the top of the base, rotating the cover down 

and snapping it into place.

5.  Secure the cover by backing out the lock-down screws using a 1/16” Allen 

wrench until they are flush with the bottom of the cover.

DRYWALL MOUNTING

1.  Place the base plate against the wall where you want to mount the sensor.

Mark the two mounting holes and the area where the wires will come 

through the wall.

2.  Drill two 3/16” holes in the center of each marked mounting hole. Insert a 

drywall anchor into each hole.

3.  Drill one 1/2” hole in the middle of the marked wiring area. Pull the wire 

through the wall and out of the 1/2” hole, leaving about six inches free.

4.  Pull the wire through the hole in the base plate.
5.  Secure the base to the drywall anchors using the #6 x 1 inch mounting screws provided.
6.  Terminate the unit according to the guidelines in the 

Termination 

section.

7.  Attach Cover by latching it to the top of the base, rotating the cover down and snapping it into place. Secure the cover by 

backing out the lock-down screws using a 1/16” Allen wrench until they are flush with the bottom of the cover.

NOTE: 

In a wall-mount application, the mixing of room air and air from within the wall cavity can lead to erroneous readings, 

condensation, and premature failure of the sensor. To prevent this condition, plug the conduit hole with insulation in the 

junction box.

Fig. 5:

 Mounting hardware is provided for 

both junction box and drywall installation 

(junction box installation shown).

Содержание BAPI-Stat 4 X-Combo

Страница 1: ...he 6 32 x 5 8 inch mounting screws provided 3 Terminate the unit according to the guidelines in the Termination section 4 Attach Cover by latching it to the top of the base rotating the cover down and...

Страница 2: ...or Override Contact referenced to CH4 TEMP See Grounding Note below CH4 TEMP Channel 4 Signal Passive Temp Sensor and or Override Contact See Grounding Note below OVR Override input to turn on the Oc...

Страница 3: ...ide and setpoint buttons See Fig 10 for a fully featured sensor NUMERICAL DISPLAY The default numerical display shows current temperature and toggles to humidity display at an adjustable rate of 1 to...

Страница 4: ...It will only change within the setpoint range that was ordered After 5 seconds of no buttons being pushed the sensor will go into the standard display or toggle mode RH SETPOINT Press the Setpoint Up...

Страница 5: ...jumper and place over one pin to end the programming mode and store all the values The sensor is now in the run mode MODE MENUS P1 Display Selection Move the Setpoint Up Down Arrows to change the disp...

Страница 6: ...0 span P11 RH Setpoint Span Low Limit Must be within the RH spans set in menu page P5 and P6 Move the UP Down arrows in 1 increments between 0 to 100 span P12 RH Setpoint Span High Limit Must be withi...

Страница 7: ...nce from wire to wire with a multimeter The meter should read greater than 10 Meg ohms open or OL depending on the meter Short the interconnecting wires together at one end Go to the other end and mea...

Страница 8: ...Humidity Range Setup Temperature Humidity or Setpoint Limits 40 to 140 F or C or 0 to 100 RH Display Setup Temp RH Setpoint with adjustable toggle rate Display Units F C RH Setpoint BAPI Man Field Con...