Installation & Operating Instructions

BAPI-Stat 4 “X-Combo”, Room %RH and Temp. Sensor

BA/BS4XC

Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI  54631 USA

Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com

7 of 8

rev. 10/28/16

27939_ins_BS4XC

Possible Solutions 

- Check for proper wire terminations and determine that the humidity input is set up correctly in the 

controller and in the building automation software.

- Check the wiring between the sensor and controller (as described above). 
- Check the sensor humidity output against a reference. Measure 

the humidity at the sensor’s location using an accurate standard. 

Disconnect the humidity channel wires and measure the humidity 

signal with a multi-meter and compare to the reference, using the 

equations at right for the reference. If the output and reference differ 

by more than 5%, call BAPI 

technical support.

- Determine if the sensor 

is exposed to an external 

source different from the room 

environment (conduit draft). 

Plug the conduit or fill the 

handy box as necessary. DO 

NOT use silicon caulk.

Voltage Humidity Equation

 RH = RH

Low

 + (V-V

Low)

 x (RH

Span

)

 

                    V

Span

RH 

= %RH at sensor

RH

Low 

= Low %RH of Span

RH

High

 

 

= High %RH of Span

RH

Span 

= RH

High

 - RH

Low

V

Low

 

= Low transmitter voltage

 

   usually=(0, 1 or 2v)

V

High 

= High transmitter voltage

 

   usually=(5 or 10v)

V

Span

  = V

High

 - V

Low

= Signal reading in volts

    4-20mA Humidity Equation

   RH = RH

Low

 + (A -4) x (RH

Span

)

 

        16

RH 

= %RH at sensor

RH

Low 

= Low %RH of Span

RH

High

 

 

= High %RH of Span

RH

Span 

= RH

High

 - RH

Low

= Signal reading in mA

Problems:

Humidity 

Reading is 

Incorrect

Possible Solutions 

- Check for proper wire terminations and determine that the temperature input is set up correctly in the 

controller and in the building automation software.

- Check the wiring between the sensor and controller. Label the terminals at the sensor end and the 

controller end.  Disconnect the interconnecting wires from the controller and the sensor.  With the 

wires disconnected, measure the resistance from wire-to-wire with a multimeter.  The meter should 

read greater than 10 Meg-ohms, open or OL depending on the meter.  Short the interconnecting 

wires together at one end.  Go to the other end and measure the resistance from wire-to-wire with a 

multimeter.  The meter should read less than 10 ohms (22 gauge or larger, 250 feet or less).  If either 

test fails, replace the wire.

- Check the sensor temperature output against a reference. Measure the temperature at the sensor’s 

location using an accurate temperature standard.  Disconnect the temperature channel wires and 

measure the temperature signal with a multi-meter and compare to the reference temperature.  For 

resistive output units, use the “Sensor Specs” tables in the “Resource Library” section of the BAPI 

website (www.bapihvac.com) for the reference. For voltage or current output units, use the equations 

below for the reference. If the output and reference differ by more than 5%, call BAPI technical support.

- Make sure that the Test and Balance switch is in the correct position.
- Make sure that the temperature sensor element leads are not touching one another.
- Determine if the sensor is exposed to an external source different from the room environment (conduit 

draft). Plug the conduit or fill the handy box as necessary. DO NOT use silicon caulk.

- Make sure that the setpoint output is correct. Remove the 

setpoint output wire (Channel 1, 2 or 3. See product label for 

configuration.) and check 

the output for the correct 

resistance, current or 

voltage output. Call BAPI 

technical support if the 

value doesn’t match the 

label.

Diagnostics - Temperature Output

Voltage Temperature Equation

    T = T

Low

 + (V-V

Low)

 x (T

Span

)

 

     V

Span

= Temperature at sensor

T

Low 

= Low temperature of span 

T

High

 

 

= High temperature of span

T

Span 

= T

High

 - T

Low

V

Low

 

= Low transmitter voltage

 

   usually=(0, 1 or 2v)

V

High 

= High transmitter voltage

 

   usually=(5 or 10v)

V

Span

  = V

High

 - V

Low

= Signal reading in volts

4-20mA Temperature Equation

 

T = T

Low

 + (A -4) x (T

Span

)

 

16

= Temperature at sensor

T

Low 

= Low temperature of span 

T

High

 

 

= High temperature of span

T

Span 

= T

High

 - T

Low

  = Signal reading in mA

Problems:

Temperature 

Reading is 

Incorrect

Setpoint 

reading is 

incorrect

Diagnostics - Humidity Output

Содержание BAPI-Stat 4 X-Combo

Страница 1: ...he 6 32 x 5 8 inch mounting screws provided 3 Terminate the unit according to the guidelines in the Termination section 4 Attach Cover by latching it to the top of the base rotating the cover down and...

Страница 2: ...or Override Contact referenced to CH4 TEMP See Grounding Note below CH4 TEMP Channel 4 Signal Passive Temp Sensor and or Override Contact See Grounding Note below OVR Override input to turn on the Oc...

Страница 3: ...ide and setpoint buttons See Fig 10 for a fully featured sensor NUMERICAL DISPLAY The default numerical display shows current temperature and toggles to humidity display at an adjustable rate of 1 to...

Страница 4: ...It will only change within the setpoint range that was ordered After 5 seconds of no buttons being pushed the sensor will go into the standard display or toggle mode RH SETPOINT Press the Setpoint Up...

Страница 5: ...jumper and place over one pin to end the programming mode and store all the values The sensor is now in the run mode MODE MENUS P1 Display Selection Move the Setpoint Up Down Arrows to change the disp...

Страница 6: ...0 span P11 RH Setpoint Span Low Limit Must be within the RH spans set in menu page P5 and P6 Move the UP Down arrows in 1 increments between 0 to 100 span P12 RH Setpoint Span High Limit Must be withi...

Страница 7: ...nce from wire to wire with a multimeter The meter should read greater than 10 Meg ohms open or OL depending on the meter Short the interconnecting wires together at one end Go to the other end and mea...

Страница 8: ...Humidity Range Setup Temperature Humidity or Setpoint Limits 40 to 140 F or C or 0 to 100 RH Display Setup Temp RH Setpoint with adjustable toggle rate Display Units F C RH Setpoint BAPI Man Field Con...

Отзывы: