Installation & Operating Instructions

BAPI-Stat 4 “X-Combo”, Room %RH and Temp. Sensor

BA/BS4XC

Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI  54631 USA

Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com

Specifications subject to change without notice.

rev. 10/28/16

27939_ins_BS4XC

8 of 8

Specifications

Supply Voltage:

  ................ 16 to 30 VDC or 18 to 30 VAC

Supply Power:

  .................. VDC = 50mA 

Temperature Sensor:

  ....... Semiconductor Band gap, ±0.5ºC 

%RH Sensor:

  .................... 2% Accuracy from 20 to 80%, Capacitive 

Available Outputs:

  ........... 3 Configurable, 1 Passive Sensor 

  Channels 1 & 2 ................ Voltage or Current 

  Channel 3......................... Voltage or Resistance 

  Channel 4......................... Passive Sensor, Dedicated override contact 

Output Signals:

  ................ Direct or reverse acting available

  Voltage ............................. VDC 0 to 5V, 1 to 5V, 0 to 10V, 2 to 10V,  Impedance>10KΩ, (ref. to common ground) 

  Current (Sourcing)  .......... 4 to 20mA, 500Ω @11.5 VDC (referenced to common ground) 

  Resistance (Setpoint) ...... Available on Ch. 3 Only 

  Passive Sensor (Ch. 4) .... Thermistor, RTD or Solid State, 

   

-CG Units, “TEMP-” terminal is Common Ground, 

   

-DF Units, “TEMP” terminals are isolated

   

Thermistor, ±0.36ºF (±0.2ºC), 

   

High Accuracy Thermistor [XP], ±0.18ºF (±0.1ºC) 

   

Platinum RTD, ±0.12%, [A] ±0.06% 

   

Nickel RTD, 1000Ω @70ºF, JCI curve

   

Solid State, AD592 or LM334 

Digital Input (DI):

  .............. Occupied dry DI input (lights BAPI-Man on display) 

Program Controls:

  ........... Requires display. See “Program Mode” section

   Offset ............................... Temperature or Humidity

   Range Setup.................... Temperature, Humidity or Setpoint - Limits: -40 to 140°F or °C or 0 to 100%RH

   Display Setup .................. Temp./%RH/Setpoint with adjustable toggle rate

   Display Units.................... °F, °C, %RH, Setpoint, BAPI-Man

Field Configuration:

  ........ J50 Jumper Pins

    Channel 4 Ground .......... CG = Jumper installed, “TEMP-” is Common Ground 

   

DF = Jumper removed, terminals Isolated (DF Mode)

   ˚F/˚C Indication ................ ˚C = Jumper installed, ˚F = Jumper removed

    Program Mode ................ ON = Jumper installed for Program Mode

   

PRG = Jumper removed for Run Mode

Optional Faceplate Controls:

 

   Setpoint ........................... Up/Down Buttons (requires display)

   Override (BAPI-Man) ....... Momentary occupied request button (5 sec), or setpoint mode change if in Setpoint Mode

   Test & Balance ................. 3-position switch for passive sensor

Optional Override:

  ........... Shunt on any one of 4 Channels 

   Face Button ..................... Used on Setpoint units

   Side Button ...................... Used on Non-Setpoint units 

Optional Comm. Jack:

 ..... Located in base: -C11 = RJ11, 4 wires  •  -C35 = 3.5mm, 3 wire  •  -C22 = RJ22, 4 wires

Optional Colored Plate:

 ....  -WMW = Warm White plate  •  -GRY = Gray plate

Test & Balance:

  ................ 3 Temp. Positions: High/Run/Low 

   Active type  ...................... Program Mode, Ch. 1, (Prog. page P15) 

   Passive Sensor ............... Optional for Ch. 4 w/ 3-Way Internal Switch

Optional Display:

  ............. LCD-Temp, RH, Setpoint, Override

   Display size  .................... 2.04”W x 1.33”H

   Digits................................ ±999.9 Digits @0.6”H 

   Resolution........................ 0.5 displayed value,  0.1 for offset adjust

   Units ................................ ˚F, ˚C, %, BAPI-Man, Setpoint

   Value Displayed ............... Always shows the value regardless of the output range

Termination:

  ..................... 8 Terminals, 16 to 22 AWG

Mounting:

  ......................... Standard 2x4” J-Box or Drywall

Enclosure Material:

  ......... ABS Plastic, UL94V-0 

Ambient (Enclosure):

  ...... 32 to 122ºF (0 to 50ºC), 0 to 95% RH, Non-condensing 

Agency: 

 ............................ RoHS

Содержание BAPI-Stat 4 X-Combo

Страница 1: ...he 6 32 x 5 8 inch mounting screws provided 3 Terminate the unit according to the guidelines in the Termination section 4 Attach Cover by latching it to the top of the base rotating the cover down and...

Страница 2: ...or Override Contact referenced to CH4 TEMP See Grounding Note below CH4 TEMP Channel 4 Signal Passive Temp Sensor and or Override Contact See Grounding Note below OVR Override input to turn on the Oc...

Страница 3: ...ide and setpoint buttons See Fig 10 for a fully featured sensor NUMERICAL DISPLAY The default numerical display shows current temperature and toggles to humidity display at an adjustable rate of 1 to...

Страница 4: ...It will only change within the setpoint range that was ordered After 5 seconds of no buttons being pushed the sensor will go into the standard display or toggle mode RH SETPOINT Press the Setpoint Up...

Страница 5: ...jumper and place over one pin to end the programming mode and store all the values The sensor is now in the run mode MODE MENUS P1 Display Selection Move the Setpoint Up Down Arrows to change the disp...

Страница 6: ...0 span P11 RH Setpoint Span Low Limit Must be within the RH spans set in menu page P5 and P6 Move the UP Down arrows in 1 increments between 0 to 100 span P12 RH Setpoint Span High Limit Must be withi...

Страница 7: ...nce from wire to wire with a multimeter The meter should read greater than 10 Meg ohms open or OL depending on the meter Short the interconnecting wires together at one end Go to the other end and mea...

Страница 8: ...Humidity Range Setup Temperature Humidity or Setpoint Limits 40 to 140 F or C or 0 to 100 RH Display Setup Temp RH Setpoint with adjustable toggle rate Display Units F C RH Setpoint BAPI Man Field Con...

Отзывы: