PROGRAM MODE MENU PAGES: (DISPLAY REQUIRED)

Note:  The J50 jumper “ ˚F/˚C “ selection determines what engineering unit is used for the following program mode.  

Make sure to selected the desired ˚F or ˚C before adjusting the program values below.

ENTERING PROGRAM MODE AND MAKING CHANGES:

1.  Install the J50 “PRG” jumper onto both pins to enter Program Mode.
2.  Press the Up/Down Buttons to advance to the desired program parameter from P1 through P17.

  (Parameters described below).
3.  Press the Override Button to select the specific program parameter to change.
4.  Change the parameter value as described in the Mode Menus section below.
5.  Press the Override Button again to set the selected parameter.
6.  Press the Up/Down Buttons to proceed to the next parameter (as in Step 3 above).
7.  When done making changes, remove the J50 “PRG” jumper (and place over one pin) to end the programming

  mode and store all the values. The sensor is now in the run mode.  

MODE MENUS

P1 - Display Selection

 (Move the Setpoint Up/Down Arrows to change the display mode. Factory default setting is 

“03”)

 

00

 = No display (Blank)

 

01

 = Temp display only 

 

02

 = %RH display only 

 

03

 = Temp and %RH display, toggling 

 

04

 = Temp Setpoint display only 

 

05

 = Temp and Temp Setpoint display, toggling

 

06

 = %RH and Temp Setpoint display, toggling

 

07

 = Temp, %RH and Temp Setpoint display, toggling

 

08

 = %RH Setpoint only

 

09

 = Temp and %RH Setpoint display, toggling

 

10

 = %RH and %RH Setpoint display, toggling

 

11

 = Temp, %RH and %RH Setpoint display, toggling 

 

12

 = Temp Setpoint and %RH Setpoint display, toggling

 

13

 = Temp, Temp Setpoint and %RH Setpoint display, toggling

 

14

 = %RH, Temp Setpoint and %RH Setpoint display, toggling

 

15

 = Temp, %RH, Temp Setpoint & %RH Setpoint display, toggling

P2 -  Display Toggle Rate (Factory default is 5 seconds)

 

 

Move the Up/Down arrows in 1 second increments up to 20 seconds between variables as selected in P1.

P3 -  Temperature Span Low Limit (Factory set per order)

 

Move the UP/Down arrows in 1˚ increments between -40 to 140 span. (˚F or ˚C must be selected first on 

Jumper J50.)

P4 -  Temperature Span High Limit (Factory set per order)

 

 

Move the UP/Down arrows in 1˚ increments between -40 to 140 span. (˚F or ˚C must be selected first on 

Jumper J50.)

Optional Technician Adjustments continued....

Содержание BAPI-Stat 4 X-Combo

Страница 1: ...he 6 32 x 5 8 inch mounting screws provided 3 Terminate the unit according to the guidelines in the Termination section 4 Attach Cover by latching it to the top of the base rotating the cover down and...

Страница 2: ...or Override Contact referenced to CH4 TEMP See Grounding Note below CH4 TEMP Channel 4 Signal Passive Temp Sensor and or Override Contact See Grounding Note below OVR Override input to turn on the Oc...

Страница 3: ...ide and setpoint buttons See Fig 10 for a fully featured sensor NUMERICAL DISPLAY The default numerical display shows current temperature and toggles to humidity display at an adjustable rate of 1 to...

Страница 4: ...It will only change within the setpoint range that was ordered After 5 seconds of no buttons being pushed the sensor will go into the standard display or toggle mode RH SETPOINT Press the Setpoint Up...

Страница 5: ...jumper and place over one pin to end the programming mode and store all the values The sensor is now in the run mode MODE MENUS P1 Display Selection Move the Setpoint Up Down Arrows to change the disp...

Страница 6: ...0 span P11 RH Setpoint Span Low Limit Must be within the RH spans set in menu page P5 and P6 Move the UP Down arrows in 1 increments between 0 to 100 span P12 RH Setpoint Span High Limit Must be withi...

Страница 7: ...nce from wire to wire with a multimeter The meter should read greater than 10 Meg ohms open or OL depending on the meter Short the interconnecting wires together at one end Go to the other end and mea...

Страница 8: ...Humidity Range Setup Temperature Humidity or Setpoint Limits 40 to 140 F or C or 0 to 100 RH Display Setup Temp RH Setpoint with adjustable toggle rate Display Units F C RH Setpoint BAPI Man Field Con...