Installation & Operating Instructions
BAPI-Stat 4 “X-Combo”, Room %RH and Temp. Sensor
BA/BS4XC
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com
Specifications subject to change without notice.
rev. 10/28/16
27939_ins_BS4XC
5 of 8
Continued on next page....
PROGRAM MODE MENU PAGES: (DISPLAY REQUIRED)
Note: The J50 jumper “ ˚F/˚C “ selection determines what engineering unit is used for the following program mode.
Make sure to selected the desired ˚F or ˚C before adjusting the program values below.
ENTERING PROGRAM MODE AND MAKING CHANGES:
1. Install the J50 “PRG” jumper onto both pins to enter Program Mode.
2. Press the Up/Down Buttons to advance to the desired program parameter from P1 through P17.
(Parameters described below).
3. Press the Override Button to select the specific program parameter to change.
4. Change the parameter value as described in the Mode Menus section below.
5. Press the Override Button again to set the selected parameter.
6. Press the Up/Down Buttons to proceed to the next parameter (as in Step 3 above).
7. When done making changes, remove the J50 “PRG” jumper (and place over one pin) to end the programming
mode and store all the values. The sensor is now in the run mode.
MODE MENUS
P1 - Display Selection
(Move the Setpoint Up/Down Arrows to change the display mode. Factory default setting is
“03”)
00
= No display (Blank)
01
= Temp display only
02
= %RH display only
03
= Temp and %RH display, toggling
04
= Temp Setpoint display only
05
= Temp and Temp Setpoint display, toggling
06
= %RH and Temp Setpoint display, toggling
07
= Temp, %RH and Temp Setpoint display, toggling
08
= %RH Setpoint only
09
= Temp and %RH Setpoint display, toggling
10
= %RH and %RH Setpoint display, toggling
11
= Temp, %RH and %RH Setpoint display, toggling
12
= Temp Setpoint and %RH Setpoint display, toggling
13
= Temp, Temp Setpoint and %RH Setpoint display, toggling
14
= %RH, Temp Setpoint and %RH Setpoint display, toggling
15
= Temp, %RH, Temp Setpoint & %RH Setpoint display, toggling
P2 - Display Toggle Rate (Factory default is 5 seconds)
Move the Up/Down arrows in 1 second increments up to 20 seconds between variables as selected in P1.
P3 - Temperature Span Low Limit (Factory set per order)
Move the UP/Down arrows in 1˚ increments between -40 to 140 span. (˚F or ˚C must be selected first on
Jumper J50.)
P4 - Temperature Span High Limit (Factory set per order)
Move the UP/Down arrows in 1˚ increments between -40 to 140 span. (˚F or ˚C must be selected first on
Jumper J50.)
Optional Technician Adjustments continued....