Note: TEACH
Selection
must be programmed to dYn tcH.
1. Enter Adjust Mode.
Method
Action
Result
SET
Button
8
Set Mode switch to ADJ
Display: Red - Signal Level; Green -
Threshold
Remote Input 9
No
action
required; sensor is ready for
Dynamic TEACH method
2. Enter Dynamic TEACH.
Method
Action
Result
SET
Button
Click the SET rocker
button
Display: Flashes "dYn tch" then holds on
"1234 dYn"
Remote Input
Single-pulse remote input
T
3. Present ON and OFF
Conditions.
Method
Action
Result
SET
Button
Present ON and OFF
conditions
Display: Red - Signal Level; Green -
Threshold
Remote Input
Present ON and OFF
conditions
4. Exit Dynamic TEACH.
Method
Action
Result
SET
Button
Click the SET rocker
button
TEACH Accepted
Displays alternate "PASS" with % Minimum
Difference
10, Sensor returns to Adjust
mode
TEACH Not Accepted
Displays alternate "FAIL" with % Minimum
Difference
10, Sensor returns to Adjust
mode
Remote Input
Single-pulse remote input
T
5. Return to RUN Mode.
Method
Action
Result
SET
Button
Move Mode switch to RUN
Display: Red - Signal Level; Green -
Threshold
Remote Input
No
action
required; sensor returns to RUN
mode
automatically
8 SET
Button:
0.04 seconds
≤
"Click"
≤
0.8 seconds
9 Remote Input: 0.04 seconds
≤
T
≤
0.8 seconds
10 See
on page 21 for more
explanation
of the % Minimum
Difference
displayed
after
the Dynamic TEACH method.
DF-G2 High Speed Expert Dual Display Fiber
Amplifier
with Dual Discrete Outputs and IO Link
www.bannerengineering.com - Tel: 763.544.3164
15