BA24
45
UK
• with voltage around 20-21Vdc, the battery is exhausted; it is possible to open the door but not to close. When
the leaf should start the motion, it does not move and the fault “exhausted battery” is signalled by 4 slow blinks
of the flashing light;
• with voltage around 16V, the battery is almost exhausted, no movement is allowed. Following a command, the
fault “exhausted battery is signalled with 4 s blinks (fast in stand-by, slow in pause). In this case, the battery
voltage could be insufficient for both the flashing light and the warning light.
RESET
By pressing simultaneously the + and – keys when the writing “PASS” appears, the default settings are restored
(only the number of performed cycles are still stored).
FLASHING LIGHT SIGNALS SUMMARY
Effect
Fault
Signal
When released it opens
5 fast flashings
Photo 2 intercepted in stand-by after a
start command
Blocked closed door
3 slow flashings
Edge intercepted in stand-by after a
start command
Blocked open door
3 slow flashings
Edge intercepted in pause after a start
command or at the beginning closing
Blocked closed door
4 fast flashings
Photo 1 test failed at opening.
Blocked open door
4 fast flashings
Photo 1 test failed at closing.
Blocked closed door
4 slow flashings
Amperometric circuit test failed at
opening
Blocked open door
4 slow flashings
Amperometric circuit test failed at
closing
Blocked closed door
3 slow flashings
Edge N.C. test failed at opening
Blocked open door
3 slow flashings
Edge N.C. test failed at closing
Blocked closed door
2 slow flashings
Edge 8K2 test failed at opening
Blocked open door
2 slow flashings
Edge 8K2 test failed at closing
The only opening is allowed
4 seconds slow flashing (*)
Backup batteries at 20-21Vdc in
stand-by after a start command
Blocked open door
4 seconds slow flashing (*)
Backup batteries at 20-21Vdc in pause
after a start command or at beginning
closing
Blocked closed door
4 seconds fast flashing (*)
Backup batteries at 16Vdc in stand-by
after a start command
Blocked open door
4 seconds slow flashing (*)
Backup batteries in pause after a start
command or at beginning closing
None
Expired maineinance
1 minute slow flashing
with closed door
(*) When backup batteries voltage is low the switching on of flashing and warning lights could not be visible.
(*) If the flashing light setting is with fixed light (C15 d), the blinking is not present but only the fixed switching on.
Содержание Gi.Bi.Di. BA24
Страница 173: ...IP55 2 10A 3 mm 2 5 mm 0 5 mm N C N A 2 1 2 3 BA24 173 GR...
Страница 190: ...START 1 2 START 2 1 START 1 C21 Y OK C6 H3 H6 ESC Gbd H3 H6 T3 T3 T3 AP CH BA24 190 GR...
Страница 191: ...24V 24V 20 21 Vdc 4 s 16V 4 s 3 PASS 5 2 start 3 start 3 start 4 1 4 1 4 4 3 N C 3 N C 2 8K2 BA24 191 GR...
Страница 196: ...NOTE BA24 196...
Страница 197: ...NOTE BA24 197...
Страница 198: ...NOTE BA24 198...