BA24
40
UK
EXTERNAL CLOCK
CLOSING ALLOWED
(set automatic closing)
C16
Y
Enables the RESERVE input for the connection of an external clock.
Operation:
When the clock closes the contact on the RESERVE input, following a
START command the door will open but not close automatically. When
the contact on the RESERVE input is opened, the door will
automatically close after the pause time.
When the door is open, the closing command can be given with “start”
if the menu is STEP-BY-STEP or STEB-BY-STEP with STOP.
WARNING: remember to preset the automatic closing, the activation of
this menu automatically defuse C17-C18.
N
Disables the RESERVE input
EXTERNAL CLOCK
CLOSING NOT ALLOWED
(set automatic closing)
C17
Y
Enables the RESERVE input for the connection of an external clock.
Operation:
When the clock closes the contact on the RESERVE input, following a
START command the door will open but not close automatically. When
the contact on the RESERVE input is opened, the door will
automatically close after the pause time.
It is not possible to activate the closing with the “start” command.
WARNING: remember to preset the automatic closing,the activation of
this menu automatically defuse C16-C18.
N
Disables the RESERVE input
EXTERNAL CLOCK
AUTOMATIC OPENING AND
CLOSING COMMAND
C18
Y
Enables the RESERVE input for the connection of an external clock.
Operation:
When the clock closes the contact on the RESERVE input, an opening
command will automatically be activated without needing to give a
START command. When the contact on the RESERVE input is opened,
the door will automatically close after the pause time.
WARNING: remember to preset the automatic closing, the activation of
this menu automatically defuse C16-C17.
N
Disables the RESERVE input
PHOTOCELL 1 TEST
C20
Y
Enables the Photocell 1 test.
The photocell 1 transmitter must be connected to the clamps 14 and 17.
Operation:
When the “Start” or the “Pedestrian” command is given, the power to
safety devices is cut off for 0,5 and then restored: if the photocell 1 input
opens and immediately returns NC the motors start, otherwise a fault will
be signalled by 4 blinks (1 sec.) of the flashing light.
N
Disables photocell 1 test.
Содержание Gi.Bi.Di. BA24
Страница 173: ...IP55 2 10A 3 mm 2 5 mm 0 5 mm N C N A 2 1 2 3 BA24 173 GR...
Страница 190: ...START 1 2 START 2 1 START 1 C21 Y OK C6 H3 H6 ESC Gbd H3 H6 T3 T3 T3 AP CH BA24 190 GR...
Страница 191: ...24V 24V 20 21 Vdc 4 s 16V 4 s 3 PASS 5 2 start 3 start 3 start 4 1 4 1 4 4 3 N C 3 N C 2 8K2 BA24 191 GR...
Страница 196: ...NOTE BA24 196...
Страница 197: ...NOTE BA24 197...
Страница 198: ...NOTE BA24 198...