9 / 20
0006081525_201112
00
02
90
687
0
ENGLISH
CONNECTING THE BURNER TO THE BOILER
ASSEMBLING THE HEAD UNIT
The combustion head is packaged separately from the burner body.
To insert the insulating flange (B) which has to be placed between
the burner and the boiler plate (A), disassemble the final part of the
combustion head.
Anchor the head unit to the boiler door as follows:
- Adjust the position of connector flange (D) by loosening the
screws (E) so that the combustion head penetrates the advised
amount into the combustion chamber as recommended by the
generator manufacturer.
- Position the insulating rope (C) on the tube unit.
Fasten the combustion head unit to the boiler (A) by means of the
stud bolts, washers and the nuts provided (F).
!
Completely seal the gap between the burner sleeve and
the hole in the refractory material inside the boiler door
with suitable material.
- Position the half-hinges (G) of the ventilating body and
combustion head so that they can be fixed using the pins (H).
- Fasten the half-hinges using the screw (M).
- Fasten the ball joint (I) to the lever (L) using the nut (N).
Содержание BGN 250 P
Страница 2: ......
Страница 57: ...57 60 0006081525_201112 SCHEMA ELETTRICO...
Страница 58: ...58 60 0006081525_201112...