BTL5-A/C/E/G1_-M_ _ _ _-B/Z-NEX-S32/KA_ _
Micropulse Linear Transducer - Rod Style
5
english
Ignition Class "n"
3
Installation (cont.)
Fig. 3-4: Magnet (optional)
BTL-P-1013-4R
3.3
Magnets, Installation
A magnet is required for each trans-
ducer. This must be ordered sepa-
rately.
➥
➥
➥
➥
➥
Fig. 3-4.
For mounting the magnet we rec-
ommend to use non-magnetizable
material.
➥
➥
➥
➥
➥
Fig. 3-1.
BTL-P-1013-4S
BTL-P-1012-4R
4
Wiring
Note the following when mak-
ing electrical connections:
System and control cabi-
net must be at the same
ground potential.
The transducer does not
have a ground terminal.
Potential compensation
must be ensured by means of a
metallic conducting installation
space.
The connecting cable
must be routed stationary
and with strain relief.
The operator must em-
ploy suitable means to
ensure that the rated volt-
age of DC 28 V is not exceeded.
To ensure the electromagnetic
compatibility (EMC) which Balluff
warrants with the CE Mark, the
following instructions must be
strictly followed.
BTL transducer and the control
must be connected using
shielded cable.
Shielding: Copper filament
braided, 85% coverage.
The shield must be tied to the
connector housing in the BKS
connector (
➥
➥
➥
➥
➥
Fig. 4-3); see in-
structions accompanying the
connector.
In the cable version the cable
shield is connected to the hous-
ing in the PG fitting.
The cable shield must be grounded
on the control side, i.e., connected
to the protection ground.
Pin assignments can be found in
➥
➥
➥
➥
➥
Table 4-1. Connections on the
controller side may vary accord-
ing to the controller and configu-
ration used.
Bild 4-1: BTL5-A11...KA_ _ with controller, wiring example
BTL5-A11-
...KA_ _
YE
GY
PK
GN
BU
BN
not used
0 V
10...0 V
0...10 V
GND
+24 V
Controller with
analog input