5.14 Humidity
5.14.1 Description
The function monitors the air humidity and informs of
changes through corresponding IO-Link events.
The humidity detection returns an immediate reaction in
the event of a critical failure. This reaction is triggered if the
humidity rises above a fixed threshold value and gives the
clear if a satisfactory humidity value is again achieved. The
status when the level is exceeded the first time is stored
permanently.
5.14.2 Process Data
Object ID
Name
Description
Direction
0x0023 (35)
Humidity Bad
Output of the current humidity evaluation; FALSE means a
humidity below above the threshold value, TRUE means a
humidity value equal to or above the threshold value.
Input
Tab. 5-66: Humidity detection – Process data
Also see section
5.14.3 ISDU
Name
Index
Subindex
Access
Length
Data Type
Data
Storage
Default
Humidity Bad 0x005C (92)
1
R
1 bit
BOOL
No
0
Operating
Hours at
Exceedance
2
R
4 bytes
UINT32
No
0
Temperature
at
Exceedance
3
R
4 bytes
INT32
No
0
Tab. 5-67: Humidity detection – ISDU
Humidity Bad
The status of the humidity is displayed as a Boolean value.
If the value is TRUE, the signal quality is above the
threshold value; if the value is FALSE, the signal quality is
below the threshold value. The evaluation includes a
hysteresis for better signal stability.
Operating Hours at Exceedance
The operating hours value at the first exceedance of the
threshold value is stored.
Temperature at Exceedance
The temperature value at the first exceedance of the
threshold value is stored.
5
Secondary Device Functions (continued)
BOS R254K-UUI-LH10-S4
Photoelectric Sensors
Содержание BOS R254K-UUI-LH10-S4
Страница 1: ...deutsch IO Link Konfiguration english IO Link Configuration BOS R254K UUI LH10 S4...
Страница 2: ...www balluff com...
Страница 3: ...BOS R254K UUI LH10 S4 IO Link Konfiguration deutsch...
Страница 4: ...www balluff com...
Страница 99: ...BOS R254K UUI LH10 S4 IO Link Configuration english...
Страница 100: ...www balluff com...
Страница 195: ......