32
english
SSC X Configuration
This ISDU is used to configure the SSC. It is possible to
set the switching logic, switching mode as well as the
hysteresis.
If the switching mode is changed, the setting of the
setpoint parameter can be adjusted:
– If changing from Two-Point or Window Mode to Single-
Point Mode, setpoint 2 is set to 0x7FFFFFFC and
thereby deactivated. In this state or in this setting, the
setting of setpoint 2 cannot take on any other value.
– If changing from Single-Point Mode to Two-Point oder
Window Mode, setpoint 2 is again activated and set to
the value of setpoint 1 minus the minimum hysteresis
and, in the subsequent process, can be taught to a
different value.
Value
Meaning
Description
Switchpoint Logic
0x00 (0)
High active
0x01 (1)
Low active
Switchpoint Mode
0x00 (0)
Deactivated
Switching channel
deactivated
0x01 (1)
Single Point
Single-Point Mode (SP1
activated)
0x02 (2)
Window
Window Mode (SP1 +
SP2 activated)
0x03 (3)
Two Point
Two-Point Mode (SP1 +
SP2 activated)
Switchpoint Hysteresis
0x0000…
0x000A
(0…10)
– Minimum: 0 (0x0000)
– Maximum: 10 (0x000A)
– Default: 5 (0x0005)
The hysteresis is used as
an integer offset to the
switching point value.
Tab. 4-15: Switching profiles – SSC Configuration Logic
4
Primary Device Functions (continued)
4.3.6 System Commands
All commands are available for LSSC (if a switching mode
that supports two setpoints was selected).
Marked commands are not available for AdSS and also not
for LSSC if a switching mode was selected that does not
support two setpoints.
Command Value Device Action
0x40 (64)
Teach Apply
– Calculates the
switching point for SP1, SP2.
0x41 (65)
Teach SP1
– Determines teach
point 1 for setpoint 1 and calculates
the switching point.
0x42 (66)
Teach SP2
– Determines teach
point 1 for setpoint 2 and calculates
the switching point
0x43 (67)
Teach SP1 TP1
– Determines teach
point 1 for setpoint 1
0x44 (68)
Teach SP1 TP2
– Determines teach
point 2 for setpoint 1
0x45 (69)
Teach SP2 TP1
– Determines teach
point 1 for setpoint 2
0x46 (70)
Teach SP2 TP2
– Determines teach
point 2 for setpoint 2
0x47 (71)
Teach SP1 Start
– Starts dynamic
teach-in for setpoint 1
0x48 (72)
Teach SP1 Stop
– Stops dynamic
teach-in for setpoint 1 and
calculates the switching point.
0x49 (73)
Teach SP2 Start
– Starts dynamic
teach-in for setpoint 2
0x4A (74)
Teach SP2 Stop
– Stops dynamic
teach-in for setpoint 2 and
calculates the switching point
0x4E (78)
Teach Reset
– Any active teach-in
process is interrupted, all
temporarily stored values are reset.
0x4F (79)
Teach Cancel
– Any active teach-in
process is interrupted.
Tab. 4-16: Switching profiles – System Commands
For an overview of all System Commands, see section 3.5
on page 19.
4.3.7 Events
Event
Code
Event
Type
Description
Device
Status
0x8DC0
(36288)
Notification
Teach-in timeout
–
The current teach
process took too
long and was
interrupted.
0 – Device
is
operating
properly.
Tab. 4-17: Basic statistics – Events
BOS R254K-UUI-LH10-S4
Photoelectric Sensors
Содержание BOS R254K-UUI-LH10-S4
Страница 1: ...deutsch IO Link Konfiguration english IO Link Configuration BOS R254K UUI LH10 S4...
Страница 2: ...www balluff com...
Страница 3: ...BOS R254K UUI LH10 S4 IO Link Konfiguration deutsch...
Страница 4: ...www balluff com...
Страница 99: ...BOS R254K UUI LH10 S4 IO Link Configuration english...
Страница 100: ...www balluff com...
Страница 195: ......