22
english
7.5.1 Measurement value configuration (MDC)
The BMP uses the measurement value to transmit the
measured position to the IO-Link master. The
measurement value can be adjusted to the respective
application using the following parameters.
Parameter
Subindex
Name
Size
Access
Values
Offset 0x00C1 (193)
0
–
4 bytes
Read/Write –600000 to +600000 μm (default: 0 μm)
Preset 0x00C2 (194)
0
–
4 bytes
Read/Write –300000 to +300000 μm (default: 0 μm)
Output Charakteristics
0x00C3 (195)
0
–
1 byte
Read/Write 0x00 (false) = Falling (zero point at end cap)
0xFF (true)
1)
= Rising (zero point on cable side)
Enable Detection Range
0x00C4 (196)
0
–
1 byte
Read/Write 0 = Detection range deactivated
0xFF (255) = Detection range activated
(default: 0xFF)
MDC Describer
0x4080 (16512)
1
Lower Limit 4 bytes
Read Only
The minimum value of the measurement value
for the current configuration.
1)
2
Upper Limit 4 bytes
Read Only
The maximum value of the measurement
value for the current configuration.
1)
3
Unit Code
2 bytes
Read Only
0x1010 (4112) = Meter
4
Scale
1 byte
Read Only
0xFA (–6) =
Measurement value × 10
–6
= Position [m]
Physical Measurement
Limits
0x0202 (514)
1
Lower Limit 4 bytes
Read/Write Limits of the raw measurement values
2)
2
Upper Limit 4 bytes
Read/Write
1)
Minimum and maximum values for the configured measuring range.
The measurement value can exceed these limits based on the
detection range
2)
These values are required for data storage to function and should not
be changed. The measuring range can be adjusted using the
Range
Teach
commands.
Tab. 7-7: MDC parameter data
The parameters can influence each other.
Therefore, it is recommended to configure the
settings in the following order: Range Teach,
Output Characteristics, Offset/Preset Teach
Range Teach
The measuring range of the BMP can be limited by
Range
Teach
. System commands
Teach Range Minimum
and
Teach Range Maximum
are available for this function. In
the newly configured measuring range, the limits of the
output value can be taken from parameter
MDC Describer
.
Output Characteristics
Using parameter
Output Characteristics
, the signal
directions of the data value can be rotated. For this
purpose, the signal is mirrored within the configured
measuring range.
Setting the Offset
An offset can be applied to the output value. To do so, the
desired value can be written in parameter
Offset
. The BMP
adds this value to the value of the measured position and
outputs it.
7
IO-Link interface (continued)
Preset Teach
The Preset Teach function enables the automatic
calculation of the offset value.
1.
Write the desired output value in parameter
Preset
.
2.
Move the target to the desired position.
3.
Execute system command
Teach Preset
.
4.
The BMP calculates the offset in order that the preset
value is output at the position being approached.
Detection Range
Furthermore, when leaving the configured measuring
range, the BMP outputs a position value until the limits of
the detection range are exceeded.
If this behavior is not required in the application, it can be
switched off using parameter
Enable Detection Range
.
A change to the measurement value
configuration influences the switching behavior.
The switching signal configuration (see sec.
7.5.2) also has to be set again.
BMP 01-EL1PP _ 1A- _ _ _ _ -00 -P _ _ /P _ _ -S4/P _ _ -S75
Magnetic Field Positioning System