IO-Link interface (continued)
Teach In operation
1.
Using Tl Select, select the desired switching signal
(1 to 4)
2.
Move the target to the switch-on position.
3.
Execute system command
Single Value Teach SP1
(0x41) (see
4.
Move the target to the switch-off position.
5.
Execute system command
Single Value Teach SP2
(0x42) (see
The steps can be checked using parameter
Teach-In Result
.
7.5.3 Output configuration
Both outputs of the BMP can be configured.
Index
Subindex
Name
Size
Access
Values
Output Type
0x00B4 (180)
1
Out 1
1 byte
Read/Write 0 = Deactivated
1 = PNP (default)
2 = NPN
3 = Push-Pull
2
Out 2
1 byte
Read/Write 0 = Deactivated
5 = Current 4 to 20 mA
6 = Voltage 0 to 10 V (default)
Tab. 7-10: Configuration of the outputs
7.5.4 Diagnostic suppression
If diagnostic functions are causing problems in the
application, these functions can be suppressed.
For diagnostics events implemented in BMP, see
.
Index
Subindex
Name
Size
Access
Values
Diagnosis
Suppression
Configuration
0x00F8 (248)
1
Suppression Level
1 byte
Read/Write 0 = All events active (default)
1 = Messages suppressed
2 = Messages and warnings suppressed
3 = All events suppressed
2
PD Invalid Suppression 1 byte
Read/Write 0x00 (0) = PD Invalid active
0xFF (255) = PD Invalid suppressed
Tab. 7-11: Diagnostic suppression
BMP 01-EL1PP _ 1A- _ _ _ _ -00 -P _ _ /P _ _ -S4/P _ _ -S75
Magnetic Field Positioning System