background image

26

english

7

 

IO-Link interface (continued)

7.5.10  Access locks (Device Access Locks)

Using this standard parameter, it is possible to activate or 

deactivate certain functions of the IO-Link device.

In BMP 01-…, there is the option to lock the function of 

the parameter manager and the button. To do so, the 

respective bit of the 2-byte value must be set to 1 (locked). 

In order to unlock the function again, the bit is set to 0.

Bit 0

Lock parameter access 

(not supported)

Bit 1

Lock parameter management 

(supported)

Bit 2

Locking the button

(supported)

Bit 3

Lock local user interface

(not supported)

Bit 4…15

Reserved

Tab. 7-13:  Locking parameter data

7.5.11  Profiles and functions (ProfileCharacteristic)

This parameter indicates which profile of the IO-Link device 

is supported.
–  Subindex 1 (DeviceProfileID):  

0×000B (measuring sensor, high resolution according 

to smart sensor profile edition 2)

–  Subindex 2 (DeviceProfileID):  

0×4000 (identification and diagnosis according to 

common profile)

–  Subindex 3 (FunctionClassID):  

0×8001 (SSC function class)

–  Subindex 4 (FunctionClassID):  

0×8004 (teach channel)

7.5.12  Process data structure (PD Input Descriptor)

This parameter describes the composition of the process 

data used.

Every part of the process data is described by 3 bytes.

Subindex

Values

Description

1

0x01

0x08

0x00

Set of Boolean

8-bit length

0-bit offset

2

0x03

0x08

0x08

Signed integer

8-bit length

8-bit offset

3

0x03

0x20

0x10

Signed integer

32-bit length

16-bit offset

Tab. 7-14:  Process data structure

Using subindex 0, the complete process data description 

can be read out (see section 

Process data (PD)

 on 

page 18).

7.5.9  Data storage

Index

Subindex Name

Size

Access

Values

Data Storage

0x0003 (3)

1

Command

1 byte

Read/Write

The 

Data Storage

 parameter is required 

by the IO-Link master for the data 

management function. This parameter 

does not offer the user a setup option.

2

State Property

1 byte

Read Only

3

Size

4 bytes

Read Only

4

Parameter Checksum

4 bytes

Read Only

5

Index List

62 bytes

Read Only

Tab. 7-12:  Data storage parameter

BMP 01-EL1PP _ 1A- _ _ _ _ -00 -P _ _ /P _ _ -S4/P _ _ -S75

Magnetic Field Positioning System

Содержание BMP 01-EL1PP 1A Series

Страница 1: ...BMP 01 EL1PP_1A _ _ _ _ 00 P_ _ S75 BMP 01 EL1PP_1A _ _ _ _ 00 P_ _ S4 BMP 01 EL1PP_1A _ _ _ _ 00 P_ _ User s Guide english...

Страница 2: ...www balluff com...

Страница 3: ...and function 7 3 1 Construction 7 3 2 Function 7 3 2 1 Analog and switching output 8 3 2 2 IO Link interface 8 3 3 LED display 8 4 Installation and connection 9 4 1 Mounting to a pneumatic cylinder u...

Страница 4: ...ccess locks Device Access Locks 26 7 5 11 Profiles and functions ProfileCharacteristic 26 7 5 12 Process data structure PD Input Descriptor 26 7 6 Diagnostic data 27 7 6 1 Diagnostic parameters 27 7 6...

Страница 5: ...ystem Condensed guide The target and mounting accessories depend on the application and are to be ordered sepa rately 1 4 Approvals and markings UL approval File no E227256 The CE Mark verifies that o...

Страница 6: ...s responsible for ensuring that local safety regulations are observed In particular the operator must take steps to ensure that a defect in the BMP will not result in hazards to persons or equipment I...

Страница 7: ...marily for the non contact detection of the piston stroke of pneumatic cylinders grippers and slides with axially magnetized permanent magnets The BMP ensures continuous absolute position measurement...

Страница 8: ...for the measured value and switching signals Functions for state monitoring Temperature detection Operating hours counter Boot cycle counter The IO Link interface is described in section 7 on page 17...

Страница 9: ...oper installation can compromise the function of the BMP and result in increased wear The target must not contact the BMP Shield any magnetic fields that can influence the measurement Position the BMP...

Страница 10: ...Align slot nuts T slot at left C slot at right in the image 3 Guide slot nuts into the slot Fig 4 4 Guiding slot nuts into the slot T slot at left C slot at right in the image Fig 4 5 Slot nuts in th...

Страница 11: ...entation of the holder see Fig 4 8 Fig 4 8 BMP Round cylinder Round cylinder holder Attaching holder to the BMP 2 Slide hose clamps over the BMP and the holders Fig 4 9 Hose clamp Applying hose clamps...

Страница 12: ...Direct and inverse mounting The BMP can be mounted directly sensing surface pointing to mounting surface or inversely Fig 4 12 N S Installation with floating target inverse mounting axially polarized...

Страница 13: ...re that there is sufficient distance between the BMP and holding cylinder and any strong external magnetic fields Cable routing Do not route cables between the BMP control system and power supply near...

Страница 14: ...t or system manufacturer 1 Check connections for tightness and correct polarity Replace damaged connections 2 Turn on the system 3 Check measurement values and adjustable parameters and readjust the B...

Страница 15: ...switching output 6 3 Switching output Switching signal factory setting Fig 6 3 active inactive Switching signal factory setting Taught in switching signal Teach 1 switch on point and Teach 2 switch of...

Страница 16: ...ton briefly Teach switch point Green off Yellow 5 Hz Red off Adjusting the switch point logic Green on off Green on Normally closed Yellow 5 Hz Green off Normally open Red 5 Hz Convert Press the butto...

Страница 17: ...sion Revision ID 0x11 Version 1 1 Amount of process data from the device to the master ProcessDataIn 6 byte 0xC5 Amount of process data from the master to the device ProcessDataOut 0 byte 0x00 Manufac...

Страница 18: ...h information for the third switch point 1 SSC 2 Switch information for the second switch point 0 SSC 1 Switch information for the first switch point SSC 1 is placed on output OUT 1 in SIO mode Tab 7...

Страница 19: ...Read Only 0 0018 24 0 Application Specific Tag Max 32 bytes Read Write X 0 0019 25 0 Function Tag Max 32 bytes Read Write X 0 001A 26 0 Location Tag Max 32 bytes Read Write X Tab 7 4 Identification d...

Страница 20: ...he currently measured position as Setpoint 1 0x42 66 SP2 Single Value Teach Saves the currently measured position as Setpoint 2 0x4E 78 Teach Reset Deletes the SP1 and SP2 values of all SSCs 0x80 128...

Страница 21: ...16385 0 1 2 3 SSC3 Configurartion 4 bytes Read Write X 0x4002 16386 0 1 2 SSC4 Parameter 8 byte Read Write X 0x4003 16387 0 1 2 3 SSC4 Configurartion 4 bytes Read Write X Device Configuration 0x00B4 1...

Страница 22: ...arameters can influence each other Therefore it is recommended to configure the settings in the following order Range Teach Output Characteristics Offset Preset Teach Range Teach The measuring range o...

Страница 23: ...385 SSC4 0x4003 16387 1 Logic 1 byte Read Write 0 Normally open NO default 1 Normally closed NC 2 Mode 1 byte Read Write 0 Deactivated 2 Window mode default 3 Hysteresis 2 bytes Read Write 100 to 3000...

Страница 24: ...ed 1 PNP default 2 NPN 3 Push Pull 2 Out 2 1 byte Read Write 0 Deactivated 5 Current 4 to 20 mA 6 Voltage 0 to 10 V default Tab 7 10 Configuration of the outputs 7 5 4 Diagnostic suppression If diagno...

Страница 25: ...25 85 C If these threshold values are exceeded or not met the BMP outputs a warning see Event list on page 27 If the internal temperature of the BMP exceeds 95 C error Excess temperature is output 7 5...

Страница 26: ...to common profile Subindex 3 FunctionClassID 0 8001 SSC function class Subindex 4 FunctionClassID 0 8004 teach channel 7 5 12 Process data structure PD Input Descriptor This parameter describes the c...

Страница 27: ...utput The transmitted process data value is 0 7FFFFFF8 or 2 147 483 640 0x8D03 Warning OUT OF RANGE MINUS The target is located outside of the detection range No valid data is output The transmitted p...

Страница 28: ...available 0x8023 Access denied 0 8030 Value out of range 0 8033 Parameter length overrun 0 8034 Parameter length underrun 0 8036 Function temporarily unavailable 0x8040 Invalid parameter set 0x8082 A...

Страница 29: ...of Ue 10 Load resistance RL Analog I 500 Ohm Output current Analog U 5 mA Load capacity of switching output 100 mA 8 4 Electrical connection Bending radius fixed routing 3 cable diameter Cable diamete...

Страница 30: ...x 10x Mounting screws 9 4 Holders for round cylinders BAM MC MP 054 01 R Order code BAM037Z 2 holders for round cylinders Fig 9 4 22 5 14 4 6 5 9 5 Holder for round cylinder 9 4 1 Hose clamps for atta...

Страница 31: ...Rising factory setting programmable Switching output 1 1 programmable switching output Setting A Characteristic and switch points adjustable using Teach In or IO Link Measuring range 4 digit e 0128 Me...

Страница 32: ...3 1 Order code 2 Type 3 Serial number Fig 11 1 Part label example 11 Appendix BMP 01 EL1PP_1A _ _ _ _ 00 P_ _ P_ _ S4 P_ _ S75 Magnetic Field Positioning System No 939733 726 EN 02 Vorserie L18 subjec...

Отзывы: