BIS V-6111 CC-Link
Processor unit
20
english
As soon as the
Dynamic mode
function is enabled, the processor unit accepts the read/write job
from the controlling system and stores it, regardless of whether a data carrier is in the active
zone of the R/W head or not. If a data carrier enters the active range of the R/W head, the stored
job is run.
Note
To achieve the read times specified on on page 42 in dynamic operation, the "Tag
type" parameter has to be set to "BIS C 32 byte" or "BIS C 64 byte" on the respective
head.
If this function is enabled, the type of the read/write head as well as the data carrier type and
serial number (UID = Unique Identifier) for the data carrier are output when CP occurs.
The length of the serial number can vary depending on the type of data carrier. To be able to
determine the length, the data is preceded by a length field.
Note
BIS C data carriers do not have a UID value.
Data for-
mat
1 byte
1 byte
1 byte 4 bytes
or 8 bytes
Meaning
Length
(number of
bytes inclu-
ding length)
Read/write head type
Data
carrier
type
UID (Mifare or
Hitag 1) or
UID (ISO 15693)
BIS VM-3_ _-001-S4 BIS VL-3_ _-001-S4
BIS C-3…
03
02
01
For this option, the antenna on the read/write head is switched on for data carrier detection only
every 200 ms. The parameters for this function are configured in the respective read/write head
module.
Transmitting power is reduced when using this parameter. The parameters for this function are
configured in the respective read/write head module and is reserved for future read/write heads.
This parameter switches off the LEDs on the respective read/write head. The parameters for this
function are configured in the respective read/write head module.
Dynamic mode
Type serial
number
Slow tag
detection
Low antenna
power
Head LEDs off
6
Startup