48
Now the next data segment can be send:
600h+ID
8
1Dh
00011101b
ccs=0, t=1,
n=6, c=1
data
x
x
x
x
x
x
CAN-ID
DLC Command
Object L Object H Sub-
Index
Byte0
Byte1
Byte2
Byte3
Table 8.31: send next segment
Within this segment it is indicated that this was the last data segment and that only the first data byte contained
valid data.
The encoder confirms:
580h+ID
8
20h
00100000b
scs=1, t=1
data
x
x
x
x
x
x
CAN-ID
DLC Command
Object L Object H Sub-
Index
Byte0
Byte1
Byte2
Byte3
Table 8.32: Acknowledgement send by the encoder
The 7 data bytes of the first segment and the single valid data byte of the data bytes represent the 8 byte "High
Precision Position Preset Value" (object 6009h).
8.3.3
Baudrate selection
The Balluff encoders provide an automatic baudrate detection. It is also possible to use a fixed baudrate which
can be set by either LSS (as described above) or SDO.
The configuration of the encoder is only possible in Pre-Operational mode. To alter the baudrate you have to
change the object 2100h into Sub-Index 00h. This can be achieved with a simple SDO write command with the
target baudrate as data.
600h+ID
8
2Fh
00h
21h
00h
Baud
00h
00h
00h
CAN-ID
DLC Command
Object L Object H Sub-
Index
Byte0
Byte1
Byte2
Byte3
Table 8.33: SDO command
– set baudrate
The following values represent the valid baud rates:
Value
Baudrate
0
1 Mbit/s
1
800 kBit/s
2
500 kBit/s
3
250 kBit/s
4
125 kBit/s
5
100 kBit/s
6
50 kBit/s
7
20 kBit/s
8
10 kBit/s
9
Auto
Table 8.34: Baudrate-coding
Содержание BDG F-NH Series
Страница 1: ...deutsch Konfigurationsanleitung english Configuration guide BDG F_ _ _ _ _ _ _ _ NH NV...
Страница 2: ...www balluff com...
Страница 3: ...deutsch Konfigurationsanleitung BDG F_ _ _ _ _ _ _ _ NH NV...
Страница 4: ...www balluff com...
Страница 67: ...english Configuration guide BDG F_ _ _ _ _ _ _ _ NH NV...
Страница 68: ...www balluff com...
Страница 105: ...www balluff com 38...
Страница 129: ......