window.
If surveillance is not required press 0 and the display will show Off. This will disable the
associated loudspeaker line faults
If surveillance is required press and release the + key until you have selected the required
frequency and mode.
Note for normal surveillance operation only use 30Hz or 20KHz.
Example 1: Frequency 30Hz, loudspeaker line A monitored only
------------------------------------------
| OUT 01|CHIME|SURV (A=00 B=00)|ANS (-00 |
| | 00|Out 09|30Hz A |Sens 00 |
------------------------------------------
Example 2: Frequency 20KHz, loudspeaker lines A and B monitored.
------------------------------------------
| OUT 01|CHIME|SURV (A=00 B=00)|ANS (-00 |
| | 00|Out 09|20K A+B |Sens 00 |
------------------------------------------
Example 3 Frequency 20KHz, loudspeaker line A and reserve amplifier monitored.
------------------------------------------
| OUT 01|CHIME|SURV (A=00 B=00)|ANS (-00 |
| | 00|Out 09|20K A+Res |Sens 00 |
------------------------------------------
Example 4 Frequency 20KHz, loudspeaker line A, line B and reserve amplifier monitored.
A&B return signals.
------------------------------------------
| OUT 01|CHIME|SURV (A=09 B=09)|ANS (-00 |
| | 00|Out 09|20K A+B+Res|Sens 00 |
------------------------------------------
↑
If surveillance is selected, move the cursor along until it flashes beneath the surveillance out
window.
Adjust the level using the + or – keys so that A and B BEL1 return signals =09, this is the typical
return value for a 10 Volt loud speaker line surveillance signal. If you have difficulty in obtaining
a return signal of 09, please check the loudspeaker line
Ambient noise sensor, only available outputs 1-16.
Volume reduction factor ( –12 minimum output), (--00 maximum output).
↓
------------------------------------------
| OUT 01|CHIME|SURV (A=00 B=00)|ANS (-00 |
| | 00|Out 09|20K A+B+Res|Sens 00 |
------------------------------------------
↑
Move the cursor along until it flashes beneath the sensor window, shown above.
If ambient noise sensing is not required or the maximum output is being set, press 0 to disable it.
This will also prevent the associated sensor fault being announced.
When the maximum levels have been set, using the + key slowly increase the value until the