background image

If the length (seconds) required is between 0-9, enter it directly using the numbered keys. Note the
cursor automatically steps to the next message. Or using the + or – keys will increase or decrease
the value between 00 and 63 seconds.

14.

 

Press the Page down key again.
The display steps to the 1

st

 page of fire panel interface mode settings, inputs 1-10.

 ------------------------------------------
| F/P  input|01|02|03|04|05|06|07|08|09|10 |
| input mode|RS|00|00|00|00|00|00|00|00|00 |
 ------------------------------------------

         

Note! Fire panel input 1 is always the reset input normally open non latching mode and can not be
changed.

Inputs 2-10 may be individually selected to 1 of 4 modes.
Mode 00 Normally open (de energized) sounder circuit latching input.
Mode 01 Normally open (de energized) sounder circuit non latching input.
Mode 02 Normally closed (energized) fail safe latching input.
Mode 03 Normally closed (energized) fail safe non latching input.

To change the mode, move the cursor along until it flashes beneath the required fire panel input.
Use keys 0-3 to select mode.

15.

 

Press the Page down key again.
The display steps to the 2

nd

 page of fire panel interface mode settings, inputs 11-20.

 ------------------------------------------
| F/P  input|11|12|13|14|15|16|17|18|19|20 |
| input mode|00|00|00|00|00|00|00|00|00|00 |
 ------------------------------------------

Inputs 11-20 may be individually selected to 1 of 4 modes.
Mode 00 Normally open (de energized) sounder circuit latching input.
Mode 01 Normally open (de energized) sounder circuit non latching input.
Mode 02 Normally closed (energized) fail safe latching input.
Mode 03 Normally closed (energized) fail safe non latching input.
To change the mode, move the cursor along until it flashes beneath the required fire panel input.
Use keys 0-3 to select mode.

16.

 

Press the Page down key again.
The display steps to the 1

st

 page of fire panel input 02 message selection, outputs 1-10

 ------------------------------------------
| F/P 02 out|01|02|03|04|05|06|07|08|09|10 |
|    message|01|02|02|02|02|02|00|00|00|00 |
 ------------------------------------------

When the fire panel input receives an alarm condition, any of the outputs can be selected to
broadcast any message.
In the example above, if input 2 receives an alarm condition, output 01 will receive message 1,
outputs 02, 03, 04, 05 & 06 will receive message 2 and outputs 07, 08, 09 & 10 will be silent.
Any of the 7 available messages 01 – 07 can be selected but in addition when sounder circuits
using continuous output for evacuate and pulsing (0.5 sec on 0.5 sec off) for alert, messages 2-5
can be selected for the alert and message 1 for the evacuate.
Note the latching mode must be used, see 14.
Message 12 = evacuate message 1, alert message 2.
Message 13 = evacuate message 1, alert message 3.
Message 14 = evacuate message 1, alert message 4.

Содержание Microdrive

Страница 1: ...ham Road Crowborough East Sussex TN6 2JR Telephone 01892 664422 Fax 01892 663146 Website www baldwinboxall co uk Email mail baldwinboxall co uk C O M M U N I C A T I O N S IBVR20 11 02 2000 VIGIL BVR2...

Страница 2: ...l of the monitoring functions and displays the system status using a 40 x 2 character LCD display and 5 front panel mounted LEDs The unit can be operated in two separate modes depending on the positio...

Страница 3: ...ATORS COMPLIES COMMON SYSTEM HEALTHY FAULT FAULT ACCEPT FAULT RESTART CPU CPU 1 2 4 5 3 6 7 8 9 0 BS5839 WITH PART 8 LAMP TEST SERIAL INTERFACE PAGE PAGE UP DOWN SYSTEM CONFIGURATION BVR20 MICRODRIVE...

Страница 4: ...hen a fault is detected see C for more details H Fault Accept Button Press to accept a fault once detected see C for more details I Lamp Test Button Press to check front panel LED and buzzer operation...

Страница 5: ...e output channel number i e 01 OUT 01 VOLUME EQUALISER SETTINGS Enter output no required Press page down 5 Press the Page down key again The display will step to the 1st page current input volume leve...

Страница 6: ...ust the chime volume Ensure the cursor is flashing beneath the chime volume window Values between 0 9 may be entered directly using the numbered keys note the cursor automatically steps to the surveil...

Страница 7: ...fier monitored A B return signals OUT 01 CHIME SURV A 09 B 09 ANS 00 00 Out 09 20K A B Res Sens 00 If surveillance is selected move the cursor along until it flashes beneath the surveillance out windo...

Страница 8: ...from maximum and 20dB below maximum Therefore if the sensor does not sense a signal the output will be 20dB below the maximum setting Pressing the Page up key enables you to step to the previous page...

Страница 9: ...f you are selecting an input channel between 1 and 9 please remember to include a 0 before the output channel number i e 08 IN 08 VOLUME EQUALISER SETTINGS Enter input no required Press page down 6 Pr...

Страница 10: ...ng the numbered keys enter your choice 0 to 3 7 Press the Page down key again The display will step to the 2nd page current attenuator compressor and chime settings for input channel 8 IN 08 ATTENUATO...

Страница 11: ...l increase or decrease the value between 00 High threshold and 15 Low threshold IN 08 ATTENUATOR COMPRESSOR CHIME 00 00 Limiter 06 Fast Off The release time may be either set Fast ideal for speech or...

Страница 12: ...an output channel number 1 31 that you wish to set up OUT 00 VOLUME EQUALISER SETTINGS Enter output no required Press page down 4 Press the Page down key again The display invites you to enter an inpu...

Страница 13: ...enter address 1 8 The Baud rates for both ports are independently set to correspond with the BVAMC DIL switch settings as shown below BVR20 setting BVAMC DIL switch settings 6 5 4 Baud rate 00 off off...

Страница 14: ...0 if this output is not required to appear on the BVAMC If the zone required is between 1 9 enter it directly using the numbered keys or using the or keys step to the zone required between 00 and 63 1...

Страница 15: ...00 Inputs 11 20 may be individually selected to 1 of 4 modes Mode 00 Normally open de energized sounder circuit latching input Mode 01 Normally open de energized sounder circuit non latching input Mo...

Страница 16: ...again The display steps to the 1st page message 01 unmonitored access selection for outputs 01 10 MES 01 out 01 02 03 04 05 06 07 08 09 10 access in 10 10 10 10 10 00 00 00 00 00 Any of the 54 access...

Страница 17: ...if input access 10 were closed to 0V via a 1K2 resistor fire microphone 01 would be broadcast to outputs 01 05 and outputs 06 10 would be silent Input 10 will be monitored and faults will be announce...

Страница 18: ...8 and inputs 1 8 37 44 on the 3rd BVRCI are used for ambient noise sensors outputs 9 16 If not required any of the above inputs may be programmed to provide access to any of the audio channels To cha...

Страница 19: ...e the cursor along until it flashes beneath the required output 1 10 window If the access input required is between 0 9 enter it directly using the numbered keys or using the or keys step to the numbe...

Страница 20: ...itors the audio output presented to the first output module and the DC bias present at the output of the digital to analogue converter which is displayed as a memory fault The dual output card BVR02 h...

Отзывы: