Message 15 = evacuate message 1, alert message 5.
To change a message, move the cursor along until it flashes beneath the required output 1-10
window.
If the message required is between 0-9, enter it directly using the numbered keys, or using the + or
– keys step to the message number required between 00 and 15.
17.
Press the Page down key again.
The display steps to the 2
nd
page of fire panel input 02 message selection, outputs 11-20.
------------------------------------------
| F/P 02 out|11|12|13|14|15|16|17|18|19|20 |
| message|00|01|02|03|04|05|00|01|02|03 |
------------------------------------------
To change a message, move the cursor along until it flashes beneath the required output 11-20
window.
If the message required is between 0-9, enter it directly using the numbered keys, or using the + or
– keys step to the message number required between 00 and 15.
18.
Press the Page down key again.
The display steps to the 1
st
page of fire panel input 03 message selection, outputs 1-10.
------------------------------------------
| F/P 03 out|01|02|03|04|05|06|07|08|09|10 |
| message|01|02|02|02|02|02|00|00|00|00 |
------------------------------------------
Repeat 16 onwards for all 20 fire panel inputs
19.
Press the Page down key again.
The display steps to the 1
st
page message 01 unmonitored access selection for outputs 01-10.
------------------------------------------
| MES 01 out|01|02|03|04|05|06|07|08|09|10 |
| access in|10|10|10|10|10|00|00|00|00|00 |
------------------------------------------
Any of the 54 access control inputs available on the 3 BVRCI termination modules may be
programmed to route any of the 23 input sources to any of the 20 outputs when the control input is
closed to 0V.
In the example above, if input access 10 were closed to 0V message 01 would be broadcast to
outputs 01-05 and outputs 06-10 would be silent. Therefore it is possible to program an access
input to select any output or group of outputs.
Note: Inputs 1-8 on the 1
st
BVRCI are used for page microphones 1-8 press to speak access.
Inputs 1-8 (19-26) on the 2
nd
BVRCI are used for ambient noise sensors outputs 1-8 and inputs 1-8
(37-44) on the 3
rd
BVRCI are used for ambient noise sensors outputs 9-16.
If not required any of the above inputs may be programmed to provide access to any of the audio
channels.
To change the access input, move the cursor along until it flashes beneath the required output 1-10
window.
If the access input required is between 0-9, enter it directly using the numbered keys, or using the
+ or – keys step to the number required between 00 and 54.