10.
Press the Page down key again.
The display steps to the 3
rd
page of serial port 1 configuration, BVAMC zone positions 11-20.
------------------------------------------
| PORT 1 out|11|12|13|14|15|16|17|18|19|20 |
| panel zone|11|12|13|14|15|16|17|18|19|20 |
------------------------------------------
Any of the 10 outputs 11-20 can be selected individually or collectively to appear as any single
zone on the BVAMC fire microphone 2.
To change a zone selection, move the cursor along until it flashes beneath the required output
window.
Press 0 if this output is not required to appear on the BVAMC.
If the zone required is between 1-9, enter it directly using the numbered keys, or using the + or –
keys step to the zone required between 00 and 63.
11.
Press the Page down key again.
The display steps to the 4
th
page of serial port 2 configuration, BVAMC zone positions 1-10.
------------------------------------------
| PORT 2 out|01|02|03|04|05|06|07|08|09|10 |
| panel zone|01|02|03|04|05|06|07|08|09|10 |
------------------------------------------
Any of the 10 outputs 1-10 can be selected individually or collectively to appear as any single zone
on the BVAMC fire microphone 4.
To change a zone selection, move the cursor along until it flashes beneath the required output
window.
Press 0 if this output is not required to appear on the BVAMC.
If the zone required is between 1-9, enter it directly using the numbered keys, or using the + or –
keys step to the zone required between 00 and 63.
12.
Press the Page down key again.
The display steps to the 5
th
page of serial port 2 configuration, BVAMC zone positions 11-20.
------------------------------------------
| PORT 2 out|11|12|13|14|15|16|17|18|19|20 |
| panel zone|11|12|13|14|15|16|17|18|19|20 |
------------------------------------------
Any of the 10 outputs 11-20 can be selected individually or collectively to appear as any single
zone on the BVAMC fire microphone. 4.
To change a zone selection, move the cursor along until it flashes beneath the required output
window.
Press 0 if this output is not required to appear on the BVAMC.
If the zone required is between 1-9, enter it directly using the numbered keys, or using the + or –
keys step to the zone required between 00 and 63.
13.
Press the Page down key again.
The display steps to the message length settings.
------------------------------------------
| MESSAGE |01|02|03|04|05|06|07|08|09|10 |
| time secs|00|00|00|00|00|00|00|00|00|00 |
------------------------------------------
Note: The dual in line switches mounted on the OPT402 for message 1 should be set to suit the
message length and the.OPT402 switches for messages 2 to 7 should be set all on
The message lengths are set as follows.
Move the cursor along until it flashes beneath the required message window.