Section 1
General Information
3-38 Receiving & Installation
MN718
Figure 3-22 15 Speed 2-Wire Control Connection Diagram
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
ENABLE
FORWARD RUN
REVERSE RUN
*
SWITCH 1
*
SWITCH 2
*
SWITCH 3
EXTERNAL TRIP
OPTO INPUT COMMON
Programmable 0–5V Output (Factory Preset: Speed)
J1
ANALOG OUT 1
ANALOG OUT 2
OPTO OUT COMMON
OPTO OUT #1
OPTO OUT #2
OPTO OUT #3
OPTO OUT #4
1
2
3
4
5
6
7
Programmable 0–5V Output (Factory Preset: Current)
Terminal Tightening Torque = 7 Lb-in (0.8 Nm).
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
23
24
25
26
27
28
29
COMMON
+24VDC
A
A
B
B
INDEX
INDEX
+5VDC
OPTO IN POWER
OPTO OUT #1 RETURN
OPTO OUT #2 RETURN
OPTO OUT #3 RETURN
OPTO OUT #4 RETURN
COMMON
A
A
B
B
INDEX
INDEX
Not Used
Encoder
Input
Note 3
Buffered
Encoder
Output
Note 4
*
SWITCH 4
ACC/DEC/“S” SELECT 1
Note 1
Note 2
*
Refer to truth table, Table 3-12.
ANALOG GND
ANALOG INPUT 1
POT REFERENCE
ANALOG INPUT +2
ANALOG INPUT –2
No Connections
Both CLOSED= Forward
Both OPEN = Stop
* All CLOSED= Fault
Reset
Notes:
1.
Refer to Analog Outputs.
2.
Refer to Opto Isolated Outputs.
3.
Refer to Encoder installation.
4.
Refer to Buffered Encoder Output.
Refer to Figure NO TAG.
J1-8
OPEN disables the control & motor coasts to a stop. CLOSED allows current to flow in
the motor and produce torque.
J1-9
CLOSED operates the motor in the Forward direction (with J1-10 open).
OPEN motor decels to stop (depending on Keypad Stop mode parameter setting).
J1-10
CLOSED operates motor in the Reverse direction (with J1-9 open).
OPEN motor decels to stop depending on Keypad Stop mode parameter setting.
J1-11 to
Selects programmed preset speeds as defined
J1-14
in Table 3-12.
J1-15
Selects ACC/DEC group. OPEN selects group 1. CLOSED selects group 2.
J1-16
OPEN causes an external trip to be received by control. The control will disable and
display external trip when programmed “ON”. When this occurs, the motor stop
command is issued, drive operation is terminated and an external trip fault is displayed
on the keypad display (also logged into the fault log).
If J1-16 is connected, you must set Level 2 Protection block, External Trip to “ON”.
J1-39 &
Jumper as shown to power the Opto Inputs from the in24VDC supply.
40
Содержание 18H Series
Страница 1: ...SERIES 18H AC Flux Vector Control Installation Operating Manual 9 97 MN718 VECTOR DRIVE ...
Страница 105: ...Section 1 General Information 5 18 Troubleshooting MN718 ...
Страница 109: ...Section 1 General Information 6 4 Manual Tuning the Series 18H Control MN718 ...
Страница 144: ...Appendix C Appendix C 1 MN718 ...