Table 3-7 Single Phase Rating Wire Size and Protection Devices - 230 VAC Controls
Control Output
P
R ti
Input Breaker
Input Fuse
Wire Gauge
p
Power Rating
p
Fast Acting
Time Delay
AWG
mm
2
1
15A
5A
5A
14
2.5
2
15A
10A
10A
14
2.5
3
15A
15A
15A
14
2.5
5
30A
30A
30A
12
4
7.5
25A
25A
25A
14
2.5
10
40A
30A
30A
12
4
15
50A
45A
45A
10
6
20
60A
45A
45A
8
10
25
70A
70A
70A
8
10
30
80A
80A
80A
6
16
40
100A
100A
100A
4
25
50
125A
125A
125A
4
25
Table 3-8 Single Phase Rating Wire Size and Protection Devices - 460 VAC Controls
Control Output
P
R ti
Input Breaker
Input Fuse
Wire Gauge
p
Power Rating
p
Fast Acting
Time Delay
AWG
mm
2
1
15A
4A
4A
14
2.5
2
15A
8A
8A
14
2.5
3
15A
10A
10A
14
2.5
5
15A
15A
15A
14
2.5
7.5
15A
15A
15A
14
2.5
10
20A
15A
15A
14
2.5
15
25A
25A
25A
14
2.5
20
30A
30A
30A
14
2.5
25
35A
30A
30A
14
2.5
30
40A
40A
40A
10
6
40
60A
50A
50A
8
10
50
70A
60A
60A
8
10
60
80A
80A
80A
6
16
Note: All wire sizes based on 75
°
C copper wire, 3% line impedance. Higher temperature smaller gauge wire may be
used per NEC and local codes. Recommended fuses/breakers are based on 25
°
C ambient, maximum
continuous control output current and no harmonic current.