Section 1
General Information
3-36 Receiving & Installation
MN718
Figure 3-21 Standard Run 3-Wire Connection Diagram
PRESET SPEED #1
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
ENABLE
FORWARD RUN
REVERSE RUN
STOP
JOG
ACCEL/DECEL
EXTERNAL TRIP
OPTO INPUT COMMON
Programmable 0–5V Output (Factory Preset: Speed)
J1
ANALOG GND
ANALOG INPUT 1
POT REFERENCE
ANALOG INPUT +2
ANALOG INPUT –2
ANALOG OUT 1
ANALOG OUT 2
OPTO OUT COMMON
OPTO OUT #1
OPTO OUT #2
OPTO OUT #3
OPTO OUT #4
1
2
3
4
5
6
7
Programmable 0–5V Output (Factory Preset: Current)
Terminal Tightening Torque = 7 Lb-in (0.8 Nm).
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
23
24
25
26
27
28
29
COMMON
+24VDC
A
A
B
B
INDEX
INDEX
+5VDC
OPTO IN POWER
OPTO OUT #1 RETURN
OPTO OUT #2 RETURN
OPTO OUT #3 RETURN
OPTO OUT #4 RETURN
COMMON
A
A
B
B
INDEX
INDEX
Not Used
Encoder
Input
Note 5
Buffered
Encoder
Output
Note 6
FAULT RESET
Note 2
Note 4
Note 3
5k
W
Command Pot
Note 1
±
5VDC,
±
10VDC or 4-20mA
Notes:
1.
Refer to Analog Inputs.
2.
Refer to Analog Outputs.
3.
Refer to Opto Isolated Outputs.
4.
Refer to Figure NO TAG for 4-20mA.
5.
Refer to Encoder installation.
6.
Refer to Buffered Encoder Output.
Refer to Figure NO TAG.
J1-8
OPEN disables the control and motor coasts to a stop.
CLOSED allows current to flow in the motor and produce torque.
J1-9
MOMENTARY CLOSED starts motor operation in the Forward direction. In JOG mode
(J1-12 CLOSED), continuous CLOSED jogs motor in the Forward direction.
J1-10
MOMENTARY CLOSED starts motor operation in the Reverse direction. In JOG mode
(J1-12 CLOSED), CONTINUOUS closed JOGS motor in the Reverse direction.
J1-11
MOMENTARY OPEN causes motor to decel to stop (depending on Keypad Stop Mode
parameter setting). Motor current continues to be applied to the motor.
J1-12
CLOSED places control in JOG mode, Forward and Reverse run are used to jog the
motor.
J1-13
OPEN selects ACC / DEC / S-CURVE group 1.
CLOSED selects group 2.
J1-14
CLOSED selects preset speed #1, (J1-12, will override this preset speed).
OPEN allows speed command from Analog input #1 or #2 or Jog.
J1-15
CLOSED to reset fault condition.
OPEN to run.
J1-16
OPEN causes an external trip to be received by control. The control will disable and
display external trip when programmed “ON”. When this occurs, the motor stop
command is issued, drive operation is terminated and an external trip fault is displayed
on the keypad display (also logged into the fault log).
If J1-16 is connected, you must set Level 2 Protection block, External Trip to “ON”.
J1–39 & 40 Jumper as shown to power the Opto Inputs from the in24VDC supply.