Test Procedure
© b2 electronic GmbH
DHV0086 Rev06
39
NOTICE
Establish secure earthing via connection
1
,
3
and
4
.
Connect HVA main earth lead
1
first and remove last!
Instrument is not earthed by connection
2
.
Step Procedure
Art� Nr�
S1
Connect all earthing cables.
• Discharge and earth the DUT complying with local safety regulations.
• Connect earthing cable to the HVA earthing connector
1
.
• Prepare earthing for measurement
3
4
.
GH0522
S2
• Connect power supply
30
.
KEK0038
S3
Connect all HV cable connections.
• Screw the HV test lead into the HVA HV output connector
10
.
• Earth the HV cable shield
2
.
• Connect the other end of the HV test lead to the DUT sheath
17
.
GH0570
GH0570
S4
Verify connections.
• Check that all cables are attached securely.
S5
Configure interlock plug.
• Verify that the HV emergency adapter is connected
47
.
If operating with remote controls (optional):
• Connect external lamps or remote switches
(
see 3.3 External Interlock and Control on page 15)
S6
Configure communication port.
For USB data transfer node, insert USB flash drive
31
.
KDD0012
S7
Turn key switch
43
to “ON” position.
KEC0007
S8
The HVA system automatically boots.
• Startup default screen appears
Select appropriate option from default screen and proceed to appropriate
section for further instructions:
•
see 5.2 Manual Test Mode on page 40
or
•
see 5.3 Automatic Test Mode on page 55