Test Procedure
© b2 electronic GmbH
DHV0086 Rev06
50
Step
Procedure
(Manual test parameters)
MS9: Pulse/Period
not applicable for DC testing, sheath fault
location
Set pulse/period and testing time:
• 1:3 / 4 s
• 1:5 / 4 s
• 1:5 / 6 s
• 1:9 / 6 s
MS10: Preset Test Voltage
(Optional- voltage can be set once test
has been initiated!)
Entering the test voltage before activating
the manual mode test by pressing “Start”
is optional. In manual mode, the voltage
can be set once the test has been initiated!
To set the test voltage before activating
the manual mode test by pressing “Start”,
rotate the navigation knob
41
until the
voltage field is selected. The dot in upper
right hand corner indicates that the test
voltage is in pre-set mode. To modify the
value, rotate navigation knob
41
To accept the value, push in knob
41
. The
dot in upper right hand disappears
indicating that the test voltage is set.
The value will also be updated if the knob
is not rotated for 2 seconds.
Содержание HVA Series
Страница 2: ...b2 electronic GmbH DHV0086 Rev06 2...
Страница 67: ...Test Procedure b2 electronic GmbH DHV0086 Rev06 67...
Страница 95: ...Reporting b2 electronic GmbH DHV0086 Rev06 95...