4.4 INSTALLATION CONDITIONS
4.4.1 Positioning in relation to the plant
To ensure optimal working conditions, the flowmeter must be installed correctly inside the system.
Correct and incorrect installation positions are described and illustrated below.
The flowmeter must remain below the hypothetical blue line (piezometric level line), which connects the two
levels of fluid to be measured (Fig. 25).
NOTE: Avoid placing the flowmeter above the piezometric level line (Fig. 26).
4.4.2 Important guidelines for correct installation
The junction box on the sensor is designed to have the IP68 protection degree only when properly
closed and tightened. The manufacturer does not assume any responsibility for an improper closing
by third parties.
For correct working conditions, please follow the important guidelines shown in the following figures.
Improper installation may result in an inaccurate measurement.
For partially filled pipes or with downward flow and free exit, the flowmeter should be placed in a U-shaped
tube (Fig. 27).
Fig. 25 | Correct position
Fig. 26 | Incorrect position
Typical installation on u-shaped pipe
Fig. 27 | Installation on U-shaped tube