AB-6569 

5)  Connect  the  cables  to  the  quick-fit  screwless  (clamp) 

terminal blocks as follows: 

   1. Insert  a  slotted  screwdriver  into  a  smaller  square  hole 

(for clamp release) on the terminal blocks located on the 
upper and lower side of the front surface. 

   2. Tilt the screwdriver while pushing it into the hole. (Make 

sure the direction to tilt, as shown in Fig. 9.) 
When the screwdriver is proceeded to the deep  end, 
the clamp is completely released. 

   3. Insert  a  bare  wire  (5-6  mm  long)  into  a  larger  square 

hole. 

   4. Pull out the screwdriver with the bare wire inserted. 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 9.  Connecting a wire to a quick-fit screwless terminal. 

Note: 

Regarding wire connection of FCU ON/OFF output, control valve 
output,  and  other  inputs,  refer  to 

Wiring  for  FCU  ON/OFF 

output, control valve output, and other inputs

 section. 

 

6)  Bind the cables with cable ties.  If an unbound cable is 

strongly pulled, Infilex FC may get damaged.  Be sure to 
bind the modular cables separately from power cables. 

 

 

 

 

 

 

 

 

 

 

 

Figure 10.  Correct and incorrect cable binding. 

 

IMPORTANT: 

Do not position any connected cable on the front 
surface of Infilex FC, as shown in Fig. 10. 

 

Precautions for Installation 

 

For Infilex FC installation, tightly fix with the screws. 

 

Leave clearance as shown in Figs. 11 and 12.  Vertically 
mount the Infilex FC (lengthwise).  Be sure to mount it in 
a  location  where  parts  identification  indication  on  the 
front surface can be checked. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

Figure 11.  Clearances for maintenance (mm): front view 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

Figure 12.  Clearances for maintenance (mm): side view 

 

To replace a currently installed IFC (Intelligent Fan Coil Unit 
Controller)  or  Microstat

  with  Infilex  FC,  a screwdriver  with 

long grip may not be usable.  In such a case, a screwdriver 
with short grip or wiring before the installation is required. 

 

1. Insert. 

2. Tilt. 

3. Insert. 

4. Pull out. 

Releasing the clamp: 
When pushing the screwdriver, tilt 
it along the curving surface inside 
the square hole. 

Correct 

cable binding 

Incorrect 

cable binding 

[1] 70 or mo

re

 

[2

] 140 or m

ore

 

[1] 20 or more 
[2] 20 or more

 

[1] 20 or more 
[2] 20 or more

 

[1] 70 or mo

re

 

[2

] 140 or m

ore

 

       Note:  [1] for 100 mm long screwdriver 
 

 

[2] for 200 mm long screwdriver 

Min 200 

Min. 120 

Min. 140 

Min. 70 

 

100 mm long 
screwdriver 

200 mm long 
screwdriver 

  Same maintenance clearance is required 

for the terminals on the lower part. 

Содержание Infilex FC

Страница 1: ...entrally monitored and controlled Features Compact size Small sized body fits inside an FCU Easy installation Connectors facilitate wiring installation Two kinds of FCU control Valve ON OFF control an...

Страница 2: ...the left warns of the risk of electric shock Notifies users that specific actions are prohibited to prevent possible danger The symbol inside graphically indicates the prohibited action For example t...

Страница 3: ...MIS cannot be mixed with SMS or DSS in the same system On LS bus max 50 remote units also called sub controllers can be connected On LC bus 2 lines for 1 channel max 50 remote units also called contro...

Страница 4: ...rol type for M H N O contact potential free Contact capacity Max 3 A AC 125 V AC Max 1 5 A AC 250 V AC Min applicable load 10 mA AC Quick fit screwless terminal block JIS 4 CVV 2 0 mm 2 or equivalent...

Страница 5: ...l between mounting screws 150 120 45 189 1 interval between mounting screws 200 Dimensions Valve ON OFF control type Figure 2 Dimensions mm Model WY5305W1000 Valve proportional control type Figure 3 D...

Страница 6: ...ater valve Connect to terminals 4 and 5 Leave terminals 6 and 7 unconnected Chilled hot water valve Connect to terminals 4 and 5 Leave terminals 6 and 7 unconnected Chilled water valve hot water valve...

Страница 7: ...ter valve Note Order of valve open close operation can be set with parameters IMPORTANT If Infilex FC is used in a 24 hour operation system be sure to fully close open the valves in 0 100 position at...

Страница 8: ...des of the M4 screw hole on a screw tab Instead of cable ties two fasteners can be used to mount Infilex FC on the threaded rod Refer to Fig 8 for mounting with cable ties fasteners Infilex FC mounted...

Страница 9: ...ition any connected cable on the front surface of Infilex FC as shown in Fig 10 Precautions for Installation For Infilex FC installation tightly fix with the screws Leave clearance as shown in Figs 11...

Страница 10: ...ased and the screwdriver remains inserted position by itself Notes A slotted screwdriver with the blade 3 5 mm wide and 0 5 mm thick straight type is applicable A screwdriver with the blade end narrow...

Страница 11: ...d inner conductors into a modular plug Figure 18 LAN cable insertion into a modular plug Pin numbers of the modular plug in Fig 18 shows the pin number arrangement when you face the side with contacts...

Страница 12: ...plug Figure 23 Modular plug Part No DY7207A0100 100 pieces set Tube Prepare tubes if necessary that meets the following specifications Figure 24 Tube commercially available Precautions for use Modular...

Страница 13: ...d to another end of the devices Max 250 m Connect a terminator to any end of the devices on the bus throughout the system 1 terminator in total as shown in Fig 29 Modular branch unit Part No DY7203A00...

Страница 14: ...so that the actual measured temperature matches the preset temperature Noise control To prevent the water flushing noise the valve is completely closed when its closing position reaches the specified...

Страница 15: ...by the center unit FCU start stop operation is not available when the setback operation is active Fan speed control Fan speed is changed over L M H AUTO with a user terminal The latest changeover ope...

Страница 16: ...1 Any combination of the following valves can be used for temperature control Chilled hot water valve chilled water valve hot water valve chilled water valve hot water valve and chilled water valve ch...

Страница 17: ...it Model DY7203A0000 Neopanel with address 1 and with address 2 are required Note that two Neopanel with address 1 connected to the Infilex FC do not work Address number is indicated on the shipping c...

Страница 18: ...Properties nc25 nciNetConfig SCPTnwrkCnfg nc165 nciDevMajVer SCPTdevMajVer nc166 nciDevMinVer SCPTdevMinVer Optional Network Variables Node object Type 0 Mandatory Network Variables nviRequest SNVT_o...

Страница 19: ...OccCmd SNVT_Occupancy nv7 nviApplicMode SNVT_hvac_mode nv8 nviSetPtOffset SNVT_temp_p nv9 nvoFanSpeed SNVT_switch nv5 nvoSpaceTemp SNVT_temp_p nv15 nvoEffectSetPt SNVT_temp_p nv16 nvoOccCmd SNVT_occup...

Страница 20: ...SNVT_obj_status Object request nvoFileStat SNVT_file_status File status Configuration network variables according to LONMARK Functional Profile Node object Variable name CP type Valid range Default v...

Страница 21: ...Default value Description SB RB MT nvoHeatOutput SNVT_lev_percent 0 00 to 100 00 0 Hot water coil output nvoCoolOutput SNVT_lev_percent 0 00 to 100 00 0 Chilled water coil output nvoFanSpeed SNVT_swit...

Страница 22: ...ory read data nvoErrorState1 UNVT_error_st1 Error indication 1 error flag nvoErrorState2 UNVT_error_st2 Error indication 2 error log nvoErrorState3 UNVT_error_st2 Error indication 3 error log nvoEepro...

Страница 23: ...AB 6569 23 This blank page was added for page layout purposes...

Страница 24: ...ardous Substances Directive RoHSD EMCD EN 61326 1 Class A Table 2 for use in an industrial electromagnetic environment LVD EN 61010 1 Overvoltage category II Pollution degree 2 RoHSD EN 50581 Infilex...

Отзывы: