Terminator 

For LonTalk protocol, terminator is required to ensure the communication reliability.  For bus topology, a terminator is connected 
at each end of the devices on the bus (= 2 terminators for bus topology).  For free topology, a terminator is connected at any end 
of the devices on the bus (= 1 terminator for free topology) throughout the whole system. 

IMPORTANT: 
Terminator types vary depending on network topology (bus topology or free topology).  Refer to the table below. 

 

Connection for bus topology (Total wiring length: Max. 900 m) 

Connect a terminator at each end of the devices on the bus (2 terminators in total) as shown in Fig. 27. 
If the wiring length is 250 m or shorter, connect a terminator at one (not both) end of the devices on the bus (1 terminator in total) 
as shown in Fig. 29.  In this case, be sure to use a free topology terminator.  

 

 

 

 

 

 

: Terminator Part No. DY7212A1101 

 

: Terminator Part No. DY7212A1100 

 

 

Connection for free topology (Total wiring length: Max. 450 m, longest wiring length between one end to another end 
of the devices: Max. 250 m) 

Connect a terminator to any end of the devices on the bus throughout the system (1 terminator in total) as shown in Fig. 29.  

 

 

 

 

 

 

 

 

 

 

 

 

 

           : Modular branch unit Part No. DY7203A0000 

 

           : Terminator Part No. DY7212A1100 

 

Figure 29.  Terminal connection example for free topology 

(Wiring length: Max. 450 m, longest wiring length between one end to another end of the devices: Max. 250 m) 

 

Terminators (modular connection type) part numbers 

 

Part number 

Indication on the labels 

Network topology 

Applicable transceiver 

DY7212A1100 

FREE 

Free topology 

TP/FT-10 channel 

DY7212A1101 

BUS 

Bus topology 

TP/FT-10 channel 

Notes: 

  Separate order is required for the terminators shown above.  Be sure to separately order your applicable terminator(s). 

  The terminators shown above are applicable only to a normal use.  Since the channel of the transceivers provided in the devices is TP/FT-10, 

they are not applicable to a special use (e.g., the same bus is used for both communication and power supply). 

Branch 

Branch 

Branch 

Branch 

Branch 

250-900 m 

Max. 250 m 

Figure 27.  Terminator connection example for bus topology 

(Wiring length: 250-900 m) 

Figure 28.  Terminator connection example for bus topology 

(Wiring length: Max. 250 m) 

Содержание Infilex FC

Страница 1: ...entrally monitored and controlled Features Compact size Small sized body fits inside an FCU Easy installation Connectors facilitate wiring installation Two kinds of FCU control Valve ON OFF control an...

Страница 2: ...the left warns of the risk of electric shock Notifies users that specific actions are prohibited to prevent possible danger The symbol inside graphically indicates the prohibited action For example t...

Страница 3: ...MIS cannot be mixed with SMS or DSS in the same system On LS bus max 50 remote units also called sub controllers can be connected On LC bus 2 lines for 1 channel max 50 remote units also called contro...

Страница 4: ...rol type for M H N O contact potential free Contact capacity Max 3 A AC 125 V AC Max 1 5 A AC 250 V AC Min applicable load 10 mA AC Quick fit screwless terminal block JIS 4 CVV 2 0 mm 2 or equivalent...

Страница 5: ...l between mounting screws 150 120 45 189 1 interval between mounting screws 200 Dimensions Valve ON OFF control type Figure 2 Dimensions mm Model WY5305W1000 Valve proportional control type Figure 3 D...

Страница 6: ...ater valve Connect to terminals 4 and 5 Leave terminals 6 and 7 unconnected Chilled hot water valve Connect to terminals 4 and 5 Leave terminals 6 and 7 unconnected Chilled water valve hot water valve...

Страница 7: ...ter valve Note Order of valve open close operation can be set with parameters IMPORTANT If Infilex FC is used in a 24 hour operation system be sure to fully close open the valves in 0 100 position at...

Страница 8: ...des of the M4 screw hole on a screw tab Instead of cable ties two fasteners can be used to mount Infilex FC on the threaded rod Refer to Fig 8 for mounting with cable ties fasteners Infilex FC mounted...

Страница 9: ...ition any connected cable on the front surface of Infilex FC as shown in Fig 10 Precautions for Installation For Infilex FC installation tightly fix with the screws Leave clearance as shown in Figs 11...

Страница 10: ...ased and the screwdriver remains inserted position by itself Notes A slotted screwdriver with the blade 3 5 mm wide and 0 5 mm thick straight type is applicable A screwdriver with the blade end narrow...

Страница 11: ...d inner conductors into a modular plug Figure 18 LAN cable insertion into a modular plug Pin numbers of the modular plug in Fig 18 shows the pin number arrangement when you face the side with contacts...

Страница 12: ...plug Figure 23 Modular plug Part No DY7207A0100 100 pieces set Tube Prepare tubes if necessary that meets the following specifications Figure 24 Tube commercially available Precautions for use Modular...

Страница 13: ...d to another end of the devices Max 250 m Connect a terminator to any end of the devices on the bus throughout the system 1 terminator in total as shown in Fig 29 Modular branch unit Part No DY7203A00...

Страница 14: ...so that the actual measured temperature matches the preset temperature Noise control To prevent the water flushing noise the valve is completely closed when its closing position reaches the specified...

Страница 15: ...by the center unit FCU start stop operation is not available when the setback operation is active Fan speed control Fan speed is changed over L M H AUTO with a user terminal The latest changeover ope...

Страница 16: ...1 Any combination of the following valves can be used for temperature control Chilled hot water valve chilled water valve hot water valve chilled water valve hot water valve and chilled water valve ch...

Страница 17: ...it Model DY7203A0000 Neopanel with address 1 and with address 2 are required Note that two Neopanel with address 1 connected to the Infilex FC do not work Address number is indicated on the shipping c...

Страница 18: ...Properties nc25 nciNetConfig SCPTnwrkCnfg nc165 nciDevMajVer SCPTdevMajVer nc166 nciDevMinVer SCPTdevMinVer Optional Network Variables Node object Type 0 Mandatory Network Variables nviRequest SNVT_o...

Страница 19: ...OccCmd SNVT_Occupancy nv7 nviApplicMode SNVT_hvac_mode nv8 nviSetPtOffset SNVT_temp_p nv9 nvoFanSpeed SNVT_switch nv5 nvoSpaceTemp SNVT_temp_p nv15 nvoEffectSetPt SNVT_temp_p nv16 nvoOccCmd SNVT_occup...

Страница 20: ...SNVT_obj_status Object request nvoFileStat SNVT_file_status File status Configuration network variables according to LONMARK Functional Profile Node object Variable name CP type Valid range Default v...

Страница 21: ...Default value Description SB RB MT nvoHeatOutput SNVT_lev_percent 0 00 to 100 00 0 Hot water coil output nvoCoolOutput SNVT_lev_percent 0 00 to 100 00 0 Chilled water coil output nvoFanSpeed SNVT_swit...

Страница 22: ...ory read data nvoErrorState1 UNVT_error_st1 Error indication 1 error flag nvoErrorState2 UNVT_error_st2 Error indication 2 error log nvoErrorState3 UNVT_error_st2 Error indication 3 error log nvoEepro...

Страница 23: ...AB 6569 23 This blank page was added for page layout purposes...

Страница 24: ...ardous Substances Directive RoHSD EMCD EN 61326 1 Class A Table 2 for use in an industrial electromagnetic environment LVD EN 61010 1 Overvoltage category II Pollution degree 2 RoHSD EN 50581 Infilex...

Отзывы: