Specifications 

Basic specifications 

Item 

Specification 

Power supply 

100 V AC to 240 V AC (85 V AC to 264 V AC) at 50 Hz/60 Hz 

Power consumption 

Valve ON/OFF control type: Max. 6 VA 
Valve proportional control type: Max. 7 VA 

Operating environmental conditions 

Temperature: 
Humidity: 
Altitude: 
Vibration: 

0 °C to 50 °C 
10 %RH to 90 %RH (non-condensing) 
2000 m or lower 
Max. 3.2 m/s² (at 10 Hz to 150 Hz) 

Transport/storage conditions 

Temperature: 
Humidity: 
Vibration: 

-20 °C to 60 °C 
5 %RH to 95 %RH (non-condensing) 
Max. 9.8 m/s² (at 10 Hz to 150 Hz) for transport 
Max. 3.2 m/s² (at 10 Hz to 150 Hz) for storage 

Mounting 

With two M4 x 10 screws 

Address setting 

Rotary switch setting 

Weight 

Valve ON/OFF control type: 270 g (main unit only) 
Valve proportional control type: 480 g (main unit only) 

 

Input/output specifications 

Connecting unit 

Input/output description 

Input/output specification 

Connection type 

Wiring specification 

Temperature sensor 

Temperature input 

Measuring range: 0 °C to 50 °C (RTD Pt100)  Connector*

1

 

LAN cable*

2

Max. 50 m 

Control valve*

4

 

ON/OFF output (for valve 
ON/OFF control type) 
Floating proportional 
output (for valve 
proportional control type) 

Normally open (N.O.) contact 
Contact capacity: Max. 0.8 A AC, 125 V AC 
 

          Max. 0.4 A AC, 250 V AC 

Min. applicable load: 10 mA AC 
For the power of valve ON/OFF control type, 
the power of the fan is used.  Select the 
power rating of the ON/OFF valve to be the 
same as the FCU power rating. 

Quick-fit 
screwless 
terminal block 

JIS*

3

 CVV 1.25 mm

2

  

or equivalent  
(for 24 V AC)/ 
JIS*

4

 CVV 2.0 mm

2

 

or equivalent  
(for 100 V AC): 
Max. 50 m 

Fan 

Fan ON/OFF output 
Fan speed changeover 
output 

Valve ON/OFF 
control type 
Valve 
proportional 
control type 
(for ‘M’/’H’) 

N.O. contact (potential free) 
Contact capacity:  
  Max. 3 A AC, 125 V AC 
  Max. 1.5 A AC, 250 V AC 
Min. applicable load: 
  10 mA AC 

Quick-fit 
screwless 
terminal block 

JIS*

4

 CVV 2.0 mm

2

 

or equivalent: 
Max. 50 m 

Valve 
proportional 
control type 
(for ‘L’) 

N.O. contact (potential free)  
Contact capacity: 
  Max. 6 A AC, 125 V AC 
  Max. 3 A AC, 250 V A 
Min. applicable load: 
  10 mA AC 

Digital user terminal 

Temperature setting 
FCU start/stop, etc. 

Serial voltage transmission 
Transmission speed: 100 bps 

Connector*

1

 

LAN cable*

2

Max. 50 m 

Analog user terminal 

FCU switch 

Potential free contact (instantaneous) 

 1 

Applied voltage/current: 12 V DC / 10 mA DC  

Connector*

1

 

LAN cable*

2

Max. 50 m 

LED output 

Output type 

Transistor output 

Output 
current/voltage 

10 mA DC / 12 V DC 

Output limited 
resistance 

1.2 k

 

Temperature setting 
input 

Potentiometer input (1 k

 to 10 k

Communication line 

LS-bus 
(LonTalk

 protocol) 

Transmission system: LonTalk

 protocol 

(TP/FT-10) 
Transmission speed: 78 kbps 

Connector*

1

 

LAN cable*

2

Max. 900 m (for bus 
topology) 

Power supply 

 

100 V AC to 240 V AC (85 V AC to 264 V AC)  M3.5 screw 

terminal block 

JIS*

4

 CVV 2.0 mm

2

 

or equivalent 

External switch, etc. 

Contact input 

Potential free contact (maintained) 

 1 

Applied voltage/current: 12 V DC / 5 mA DC 

Quick-fit 
screwless 
terminal block 

JIS*

4

 CVV 1.25 mm

2

 

or equivalent: 
Max. 50 m 

Notes: 

1  For connector connection, use Stewart Connector’s Plug: Model 940-SP-3088R. 

This plug is also available at Azbil Corporation. (Part No. DY7207A0100, 100 pieces/set) 

2  LAN cable compliant with EIA/TIA-568 Category 3 or over (

0.5 mm 

 4 poles) is required. 

For 

1 and 

2, the cable with connector (Part No. DY7210) and the short cable with connector (Part No. DY7220) are available. 

3  JIS: Japanese Industrial Standards. 

4  Proportional control valve with less than 30-second operating time (for full stroke) is not applicable.  Ask our sales personnel for details. 

Содержание Infilex FC

Страница 1: ...entrally monitored and controlled Features Compact size Small sized body fits inside an FCU Easy installation Connectors facilitate wiring installation Two kinds of FCU control Valve ON OFF control an...

Страница 2: ...the left warns of the risk of electric shock Notifies users that specific actions are prohibited to prevent possible danger The symbol inside graphically indicates the prohibited action For example t...

Страница 3: ...MIS cannot be mixed with SMS or DSS in the same system On LS bus max 50 remote units also called sub controllers can be connected On LC bus 2 lines for 1 channel max 50 remote units also called contro...

Страница 4: ...rol type for M H N O contact potential free Contact capacity Max 3 A AC 125 V AC Max 1 5 A AC 250 V AC Min applicable load 10 mA AC Quick fit screwless terminal block JIS 4 CVV 2 0 mm 2 or equivalent...

Страница 5: ...l between mounting screws 150 120 45 189 1 interval between mounting screws 200 Dimensions Valve ON OFF control type Figure 2 Dimensions mm Model WY5305W1000 Valve proportional control type Figure 3 D...

Страница 6: ...ater valve Connect to terminals 4 and 5 Leave terminals 6 and 7 unconnected Chilled hot water valve Connect to terminals 4 and 5 Leave terminals 6 and 7 unconnected Chilled water valve hot water valve...

Страница 7: ...ter valve Note Order of valve open close operation can be set with parameters IMPORTANT If Infilex FC is used in a 24 hour operation system be sure to fully close open the valves in 0 100 position at...

Страница 8: ...des of the M4 screw hole on a screw tab Instead of cable ties two fasteners can be used to mount Infilex FC on the threaded rod Refer to Fig 8 for mounting with cable ties fasteners Infilex FC mounted...

Страница 9: ...ition any connected cable on the front surface of Infilex FC as shown in Fig 10 Precautions for Installation For Infilex FC installation tightly fix with the screws Leave clearance as shown in Figs 11...

Страница 10: ...ased and the screwdriver remains inserted position by itself Notes A slotted screwdriver with the blade 3 5 mm wide and 0 5 mm thick straight type is applicable A screwdriver with the blade end narrow...

Страница 11: ...d inner conductors into a modular plug Figure 18 LAN cable insertion into a modular plug Pin numbers of the modular plug in Fig 18 shows the pin number arrangement when you face the side with contacts...

Страница 12: ...plug Figure 23 Modular plug Part No DY7207A0100 100 pieces set Tube Prepare tubes if necessary that meets the following specifications Figure 24 Tube commercially available Precautions for use Modular...

Страница 13: ...d to another end of the devices Max 250 m Connect a terminator to any end of the devices on the bus throughout the system 1 terminator in total as shown in Fig 29 Modular branch unit Part No DY7203A00...

Страница 14: ...so that the actual measured temperature matches the preset temperature Noise control To prevent the water flushing noise the valve is completely closed when its closing position reaches the specified...

Страница 15: ...by the center unit FCU start stop operation is not available when the setback operation is active Fan speed control Fan speed is changed over L M H AUTO with a user terminal The latest changeover ope...

Страница 16: ...1 Any combination of the following valves can be used for temperature control Chilled hot water valve chilled water valve hot water valve chilled water valve hot water valve and chilled water valve ch...

Страница 17: ...it Model DY7203A0000 Neopanel with address 1 and with address 2 are required Note that two Neopanel with address 1 connected to the Infilex FC do not work Address number is indicated on the shipping c...

Страница 18: ...Properties nc25 nciNetConfig SCPTnwrkCnfg nc165 nciDevMajVer SCPTdevMajVer nc166 nciDevMinVer SCPTdevMinVer Optional Network Variables Node object Type 0 Mandatory Network Variables nviRequest SNVT_o...

Страница 19: ...OccCmd SNVT_Occupancy nv7 nviApplicMode SNVT_hvac_mode nv8 nviSetPtOffset SNVT_temp_p nv9 nvoFanSpeed SNVT_switch nv5 nvoSpaceTemp SNVT_temp_p nv15 nvoEffectSetPt SNVT_temp_p nv16 nvoOccCmd SNVT_occup...

Страница 20: ...SNVT_obj_status Object request nvoFileStat SNVT_file_status File status Configuration network variables according to LONMARK Functional Profile Node object Variable name CP type Valid range Default v...

Страница 21: ...Default value Description SB RB MT nvoHeatOutput SNVT_lev_percent 0 00 to 100 00 0 Hot water coil output nvoCoolOutput SNVT_lev_percent 0 00 to 100 00 0 Chilled water coil output nvoFanSpeed SNVT_swit...

Страница 22: ...ory read data nvoErrorState1 UNVT_error_st1 Error indication 1 error flag nvoErrorState2 UNVT_error_st2 Error indication 2 error log nvoErrorState3 UNVT_error_st2 Error indication 3 error log nvoEepro...

Страница 23: ...AB 6569 23 This blank page was added for page layout purposes...

Страница 24: ...ardous Substances Directive RoHSD EMCD EN 61326 1 Class A Table 2 for use in an industrial electromagnetic environment LVD EN 61010 1 Overvoltage category II Pollution degree 2 RoHSD EN 50581 Infilex...

Отзывы: