AB-6569 

11 

Modular Connector Connection 

Modular  connector  is  composed  of  a  modular  plug  (male) 
and a modular jack (female).  Modular jacks are provided on 
Infilex FC, and modular plugs will be crimped on LAN cables 
as requires.  Refer to the following procedure for crimping the 
modular plugs on the LAN cables and connecting them to the 
modular jacks. 
For  modular  plugs,  refer  to  the  note  1  in 

Specifications

 

section. 

 

Procedure for modular connector connection 

1)  Strip outer sheath of a LAN cable end.  Be sure not to 

scratch  or  peel  off  any  inner  conductor  sheath  when 
stripping the outer sheath. 

 

 

 

 

 

 

 

Figure 16.  Stripping the outer sheath 

 

Make sure there are 8 inner conductors inside the outer 
sheath. 

 

2)  Align the 8 inner conductors in a order specified by the 

LAN cable manufacturer. 

 

 

 

 

Figure 17.  Alignment of the inner conductors 

 

Alignment of the LAN cable inner conductors is shown in 
the table below. 

Modular pin 

number 

LAN cable inner 

conductor alignment 

 

Color alignment example 

Line 1 of pair 2 

Orange 

Line 2 of pair 2 

White and orange 

Line 1 of pair 3 

Green 

Line 2 of pair 1 

Blue and white 

Line 1 of pair 1 

Blue 

Line 2 of pair 3 

Green and white 

Line 1 of pair 4 

Brown 

Line 2 of pair 4 

Brown and white 

 Note: 

Color  alignment  shown  above  may  not  agree  with  your  LAN 
cable  specification.    Ask  your  LAN  cable  manufacturer  for  the 
latest specification. 

3)  Insert the aligned inner conductors into a modular plug. 

 

 

 

 

 

 

 

 

 

 
 

Figure 18.  LAN cable insertion into a modular plug 

 

Pin numbers of the modular plug in Fig. 18 shows the pin 
number  arrangement  when  you  face  the  side  with 
contacts and cable stopper. 
Before inserting the inner conductors into a modular plug, 
even out the length with a nipper.  Note that the modular 
plug  may  not  be  crimped  on  inner  conductors  stripped 
too long. 

 

4)  Crimp  the  modular  plug  with  the  crimping  tool.  

Completely insert the inner conductors into the modular 
plug so that the contacts of the modular plug stick into 
the inner conductors when the modular plug is crimped.  
Crimped modular plug is secured on the LAN cable with 
the  cable  stopper  of  the  modular  pug.    Check  the 
contacts  and  the  cable  stopper  when  crimping  the 
modular plug. 

 

5)  Follow 1) to 4) for the other end of the LAN cable. 

 

6)  Check continuity of the LAN cable.  Modular continuity 

tester  (Part  No.  DY7206A0000)  facilitates  continuity 
check.    At  the  same  time,  make  sure  that  the  inner 
conductors are in order with the modular plug contacts 
sticking  in  the  conductors  and  that  there  is  no  cable 
damage or disconnection. 

 

7)  Connect the modular plugs to the modular jacks.  When 

the continuity check is successfully completed, insert the 
LAN cable modular plugs into the modular jacks of Infilex 
FC and of user terminal/temperature sensor. 
Be sure to completely insert a modular plug until it clicks. 

 

LAN cable 

Pin numbers 

 12345678 

Contacts  Cable stopper 

Insert. 

LAN cable 

10 

 3 mm 

(For the recommended  
modular plug) 

LAN cable 

Modular 

plug 

LAN cable 

8 inner 
conductors 

Содержание Infilex FC

Страница 1: ...entrally monitored and controlled Features Compact size Small sized body fits inside an FCU Easy installation Connectors facilitate wiring installation Two kinds of FCU control Valve ON OFF control an...

Страница 2: ...the left warns of the risk of electric shock Notifies users that specific actions are prohibited to prevent possible danger The symbol inside graphically indicates the prohibited action For example t...

Страница 3: ...MIS cannot be mixed with SMS or DSS in the same system On LS bus max 50 remote units also called sub controllers can be connected On LC bus 2 lines for 1 channel max 50 remote units also called contro...

Страница 4: ...rol type for M H N O contact potential free Contact capacity Max 3 A AC 125 V AC Max 1 5 A AC 250 V AC Min applicable load 10 mA AC Quick fit screwless terminal block JIS 4 CVV 2 0 mm 2 or equivalent...

Страница 5: ...l between mounting screws 150 120 45 189 1 interval between mounting screws 200 Dimensions Valve ON OFF control type Figure 2 Dimensions mm Model WY5305W1000 Valve proportional control type Figure 3 D...

Страница 6: ...ater valve Connect to terminals 4 and 5 Leave terminals 6 and 7 unconnected Chilled hot water valve Connect to terminals 4 and 5 Leave terminals 6 and 7 unconnected Chilled water valve hot water valve...

Страница 7: ...ter valve Note Order of valve open close operation can be set with parameters IMPORTANT If Infilex FC is used in a 24 hour operation system be sure to fully close open the valves in 0 100 position at...

Страница 8: ...des of the M4 screw hole on a screw tab Instead of cable ties two fasteners can be used to mount Infilex FC on the threaded rod Refer to Fig 8 for mounting with cable ties fasteners Infilex FC mounted...

Страница 9: ...ition any connected cable on the front surface of Infilex FC as shown in Fig 10 Precautions for Installation For Infilex FC installation tightly fix with the screws Leave clearance as shown in Figs 11...

Страница 10: ...ased and the screwdriver remains inserted position by itself Notes A slotted screwdriver with the blade 3 5 mm wide and 0 5 mm thick straight type is applicable A screwdriver with the blade end narrow...

Страница 11: ...d inner conductors into a modular plug Figure 18 LAN cable insertion into a modular plug Pin numbers of the modular plug in Fig 18 shows the pin number arrangement when you face the side with contacts...

Страница 12: ...plug Figure 23 Modular plug Part No DY7207A0100 100 pieces set Tube Prepare tubes if necessary that meets the following specifications Figure 24 Tube commercially available Precautions for use Modular...

Страница 13: ...d to another end of the devices Max 250 m Connect a terminator to any end of the devices on the bus throughout the system 1 terminator in total as shown in Fig 29 Modular branch unit Part No DY7203A00...

Страница 14: ...so that the actual measured temperature matches the preset temperature Noise control To prevent the water flushing noise the valve is completely closed when its closing position reaches the specified...

Страница 15: ...by the center unit FCU start stop operation is not available when the setback operation is active Fan speed control Fan speed is changed over L M H AUTO with a user terminal The latest changeover ope...

Страница 16: ...1 Any combination of the following valves can be used for temperature control Chilled hot water valve chilled water valve hot water valve chilled water valve hot water valve and chilled water valve ch...

Страница 17: ...it Model DY7203A0000 Neopanel with address 1 and with address 2 are required Note that two Neopanel with address 1 connected to the Infilex FC do not work Address number is indicated on the shipping c...

Страница 18: ...Properties nc25 nciNetConfig SCPTnwrkCnfg nc165 nciDevMajVer SCPTdevMajVer nc166 nciDevMinVer SCPTdevMinVer Optional Network Variables Node object Type 0 Mandatory Network Variables nviRequest SNVT_o...

Страница 19: ...OccCmd SNVT_Occupancy nv7 nviApplicMode SNVT_hvac_mode nv8 nviSetPtOffset SNVT_temp_p nv9 nvoFanSpeed SNVT_switch nv5 nvoSpaceTemp SNVT_temp_p nv15 nvoEffectSetPt SNVT_temp_p nv16 nvoOccCmd SNVT_occup...

Страница 20: ...SNVT_obj_status Object request nvoFileStat SNVT_file_status File status Configuration network variables according to LONMARK Functional Profile Node object Variable name CP type Valid range Default v...

Страница 21: ...Default value Description SB RB MT nvoHeatOutput SNVT_lev_percent 0 00 to 100 00 0 Hot water coil output nvoCoolOutput SNVT_lev_percent 0 00 to 100 00 0 Chilled water coil output nvoFanSpeed SNVT_swit...

Страница 22: ...ory read data nvoErrorState1 UNVT_error_st1 Error indication 1 error flag nvoErrorState2 UNVT_error_st2 Error indication 2 error log nvoErrorState3 UNVT_error_st2 Error indication 3 error log nvoEepro...

Страница 23: ...AB 6569 23 This blank page was added for page layout purposes...

Страница 24: ...ardous Substances Directive RoHSD EMCD EN 61326 1 Class A Table 2 for use in an industrial electromagnetic environment LVD EN 61010 1 Overvoltage category II Pollution degree 2 RoHSD EN 50581 Infilex...

Отзывы: