Check and Setting 

The  following  check  and  settings  must  be  performed  by  a 
technical engineer. 

 

LED indication 

After the power is applied to Infilex FC, check that the status 
indicator LED blinks in approx. 10 seconds.  If it stays ON, 
Infilex FC is in an abnormal status.  The LED stays ON for 
seconds immediately after the power is applied, which does 
not indicate an error.  LED indication is described on the front 
surface of Infilex FC. (See Figs. 30 to 32.) 

 

 

 

 

 

 

 

 

 

 

 

Figure 30.  LED indication 

 

Status 

LED indication (

: ON / 

: OFF) 

Normal 

Normal 
 

Power OFF 

Power 
Off 

LS-bus error 

LS-bus 
Err 

Initializing / 
Error 

Error 1 
 

Minor error 

Error 2 
 
 
 

Figure 31.  Descriptions of red LED indication (status) 

 

Status 

LED indication (

: ON / 

: OFF) 

Normal 

Normal 
 

Applicationless 

Appli-less 
 
 

Unconfigured 

Unconfig 
 
 

LS-bus error 

Any indication other than the above. 

Figure 32.  Descriptions of green LED indication 

(Communication with LonTalk protocol) 

 

Address setting 

Two address setting dials are located on the front surface of 
Infilex FC.  The allow of the upper dial (with ‘x10’) indicates 
tens, and the allow of the lower dial (with ‘x1’) indicates ones. 
For setting the address, use a small Phillips screwdriver to 
turn the dial. 

Parameter setting 

Infilex FC parameters are set in response to the size and type 
of FCU, room characteristics, and applications. 
 

To Connect Two User Terminals  
(for Remote Control) 

Up to two digital user terminals (Neopanel Model QY7205C) 
can be connected to one Infilex FC. 

To connect the two user terminals 

Modular branch unit (Model DY7203A0000) 

Neopanel with address 1 and with address 2 

are required.  

Note  that  two  Neopanel  with  address  1  connected  to  the 
Infilex FC do not work.  Address number is indicated on the 
shipping  carton  and  on  the  label  attached  to  the  inside 
surface  of  the  Neopanel  main  unit  (with  the  base  cover 
removed). 

Notes: 

  The  latest  FCU  start/stop  operation  or  temperature  setting 

operation  with  a  Neopanel  or  with  the  BMS  center  unit  takes 
priority. 

  Neopanel  with  address  2  does  not  have  a  temperature 

measuring function. 

 
Connection of Data Setter for LonTalk Protocol 

Connect  the  CompactFlash

  memory  type  Data  Setter 

(Model  QY5111B)  for  LonTalk  protocol  to  LS-bus  port  of 
Infilex  FC  with  the  Data  Setter  adaptor  (Part  No. 
DY5301S0000, with separate order required). 
For  details  of  the  Data  Setter  adaptor,  refer  to  its 
Specifications manual. 

 

 

 

 

 

 

 

Note: 

Parameters of a remote unit on LS-bus (sub-controller) can also 
be set and modified with the Data Setter with Data Setter adaptor 
connected  on  a  remote  unit  on  LC-bus  (controller).    Refer  to 
Specifications/Instructions of the respective controllers. 

Figure 33.  Connection example of Data Setter with Data setter 

adaptor to LS-bus port of Infilex FC 

 

Address 
setting dial 

Valve proportional  

control type 

LED (red) 
LED (green) 

Valve ON/OFF 

control type 

LED (red) 

Descriptions of 

LED indication 

Address 
setting dial 

LED (green) 

1s 

1s 

0.25s  0.25s 

1s 

0.25s 

0.25s 

0.25s 

3s 

1s 

1s 

Infilex FC

 

Model WY5305

 

Infilex SC 

Model WY5307

 

Infilex VC 

Model WY5306

 

Data Setter 

adaptor 

Model DY5301S 

Data Setter 

Model QY5111B

 

LS-bus (LonTalk protocol) 

(For setting Infilex FC and the remote units 
connected on LS-bus: 
Connect Data Setter with Data Setter adaptor
to LS-bus port of Infilex FC.) 

Содержание Infilex FC

Страница 1: ...entrally monitored and controlled Features Compact size Small sized body fits inside an FCU Easy installation Connectors facilitate wiring installation Two kinds of FCU control Valve ON OFF control an...

Страница 2: ...the left warns of the risk of electric shock Notifies users that specific actions are prohibited to prevent possible danger The symbol inside graphically indicates the prohibited action For example t...

Страница 3: ...MIS cannot be mixed with SMS or DSS in the same system On LS bus max 50 remote units also called sub controllers can be connected On LC bus 2 lines for 1 channel max 50 remote units also called contro...

Страница 4: ...rol type for M H N O contact potential free Contact capacity Max 3 A AC 125 V AC Max 1 5 A AC 250 V AC Min applicable load 10 mA AC Quick fit screwless terminal block JIS 4 CVV 2 0 mm 2 or equivalent...

Страница 5: ...l between mounting screws 150 120 45 189 1 interval between mounting screws 200 Dimensions Valve ON OFF control type Figure 2 Dimensions mm Model WY5305W1000 Valve proportional control type Figure 3 D...

Страница 6: ...ater valve Connect to terminals 4 and 5 Leave terminals 6 and 7 unconnected Chilled hot water valve Connect to terminals 4 and 5 Leave terminals 6 and 7 unconnected Chilled water valve hot water valve...

Страница 7: ...ter valve Note Order of valve open close operation can be set with parameters IMPORTANT If Infilex FC is used in a 24 hour operation system be sure to fully close open the valves in 0 100 position at...

Страница 8: ...des of the M4 screw hole on a screw tab Instead of cable ties two fasteners can be used to mount Infilex FC on the threaded rod Refer to Fig 8 for mounting with cable ties fasteners Infilex FC mounted...

Страница 9: ...ition any connected cable on the front surface of Infilex FC as shown in Fig 10 Precautions for Installation For Infilex FC installation tightly fix with the screws Leave clearance as shown in Figs 11...

Страница 10: ...ased and the screwdriver remains inserted position by itself Notes A slotted screwdriver with the blade 3 5 mm wide and 0 5 mm thick straight type is applicable A screwdriver with the blade end narrow...

Страница 11: ...d inner conductors into a modular plug Figure 18 LAN cable insertion into a modular plug Pin numbers of the modular plug in Fig 18 shows the pin number arrangement when you face the side with contacts...

Страница 12: ...plug Figure 23 Modular plug Part No DY7207A0100 100 pieces set Tube Prepare tubes if necessary that meets the following specifications Figure 24 Tube commercially available Precautions for use Modular...

Страница 13: ...d to another end of the devices Max 250 m Connect a terminator to any end of the devices on the bus throughout the system 1 terminator in total as shown in Fig 29 Modular branch unit Part No DY7203A00...

Страница 14: ...so that the actual measured temperature matches the preset temperature Noise control To prevent the water flushing noise the valve is completely closed when its closing position reaches the specified...

Страница 15: ...by the center unit FCU start stop operation is not available when the setback operation is active Fan speed control Fan speed is changed over L M H AUTO with a user terminal The latest changeover ope...

Страница 16: ...1 Any combination of the following valves can be used for temperature control Chilled hot water valve chilled water valve hot water valve chilled water valve hot water valve and chilled water valve ch...

Страница 17: ...it Model DY7203A0000 Neopanel with address 1 and with address 2 are required Note that two Neopanel with address 1 connected to the Infilex FC do not work Address number is indicated on the shipping c...

Страница 18: ...Properties nc25 nciNetConfig SCPTnwrkCnfg nc165 nciDevMajVer SCPTdevMajVer nc166 nciDevMinVer SCPTdevMinVer Optional Network Variables Node object Type 0 Mandatory Network Variables nviRequest SNVT_o...

Страница 19: ...OccCmd SNVT_Occupancy nv7 nviApplicMode SNVT_hvac_mode nv8 nviSetPtOffset SNVT_temp_p nv9 nvoFanSpeed SNVT_switch nv5 nvoSpaceTemp SNVT_temp_p nv15 nvoEffectSetPt SNVT_temp_p nv16 nvoOccCmd SNVT_occup...

Страница 20: ...SNVT_obj_status Object request nvoFileStat SNVT_file_status File status Configuration network variables according to LONMARK Functional Profile Node object Variable name CP type Valid range Default v...

Страница 21: ...Default value Description SB RB MT nvoHeatOutput SNVT_lev_percent 0 00 to 100 00 0 Hot water coil output nvoCoolOutput SNVT_lev_percent 0 00 to 100 00 0 Chilled water coil output nvoFanSpeed SNVT_swit...

Страница 22: ...ory read data nvoErrorState1 UNVT_error_st1 Error indication 1 error flag nvoErrorState2 UNVT_error_st2 Error indication 2 error log nvoErrorState3 UNVT_error_st2 Error indication 3 error log nvoEepro...

Страница 23: ...AB 6569 23 This blank page was added for page layout purposes...

Страница 24: ...ardous Substances Directive RoHSD EMCD EN 61326 1 Class A Table 2 for use in an industrial electromagnetic environment LVD EN 61010 1 Overvoltage category II Pollution degree 2 RoHSD EN 50581 Infilex...

Отзывы: