Check and Setting
The following check and settings must be performed by a
technical engineer.
LED indication
After the power is applied to Infilex FC, check that the status
indicator LED blinks in approx. 10 seconds. If it stays ON,
Infilex FC is in an abnormal status. The LED stays ON for
seconds immediately after the power is applied, which does
not indicate an error. LED indication is described on the front
surface of Infilex FC. (See Figs. 30 to 32.)
Figure 30. LED indication
Status
LED indication (
□
: ON /
■
: OFF)
Normal
Normal
Power OFF
Power
Off
LS-bus error
LS-bus
Err
Initializing /
Error
Error 1
Minor error
Error 2
Figure 31. Descriptions of red LED indication (status)
Status
LED indication (
□
: ON /
■
: OFF)
Normal
Normal
Applicationless
Appli-less
Unconfigured
Unconfig
LS-bus error
Any indication other than the above.
Figure 32. Descriptions of green LED indication
(Communication with LonTalk protocol)
Address setting
Two address setting dials are located on the front surface of
Infilex FC. The allow of the upper dial (with ‘x10’) indicates
tens, and the allow of the lower dial (with ‘x1’) indicates ones.
For setting the address, use a small Phillips screwdriver to
turn the dial.
Parameter setting
Infilex FC parameters are set in response to the size and type
of FCU, room characteristics, and applications.
To Connect Two User Terminals
(for Remote Control)
Up to two digital user terminals (Neopanel Model QY7205C)
can be connected to one Infilex FC.
To connect the two user terminals
-
Modular branch unit (Model DY7203A0000)
-
Neopanel with address 1 and with address 2
are required.
Note that two Neopanel with address 1 connected to the
Infilex FC do not work. Address number is indicated on the
shipping carton and on the label attached to the inside
surface of the Neopanel main unit (with the base cover
removed).
Notes:
The latest FCU start/stop operation or temperature setting
operation with a Neopanel or with the BMS center unit takes
priority.
Neopanel with address 2 does not have a temperature
measuring function.
Connection of Data Setter for LonTalk Protocol
Connect the CompactFlash
memory type Data Setter
(Model QY5111B) for LonTalk protocol to LS-bus port of
Infilex FC with the Data Setter adaptor (Part No.
DY5301S0000, with separate order required).
For details of the Data Setter adaptor, refer to its
Specifications manual.
Note:
Parameters of a remote unit on LS-bus (sub-controller) can also
be set and modified with the Data Setter with Data Setter adaptor
connected on a remote unit on LC-bus (controller). Refer to
Specifications/Instructions of the respective controllers.
Figure 33. Connection example of Data Setter with Data setter
adaptor to LS-bus port of Infilex FC
Address
setting dial
Valve proportional
control type
LED (red)
LED (green)
Valve ON/OFF
control type
LED (red)
Descriptions of
LED indication
Address
setting dial
LED (green)
1s
1s
0.25s 0.25s
1s
0.25s
0.25s
0.25s
3s
1s
1s
Infilex FC
Model WY5305
Infilex SC
Model WY5307
Infilex VC
Model WY5306
Data Setter
adaptor
Model DY5301S
Data Setter
Model QY5111B
LS-bus (LonTalk protocol)
(For setting Infilex FC and the remote units
connected on LS-bus:
Connect Data Setter with Data Setter adaptor
to LS-bus port of Infilex FC.)