Mount Infilex FC with the front surface facing horizontal 
direction  unless  it  is  protected  in  a  dust-proof  housing. 
(See ‘B’ in Fig. 13.)  If the Infilex FC is mounted with its 
front surface facing the vertical direction (upwards), dust 
may accumulate on the connectors. (See ‘A’ in Fig. 13.) 

 

 

 

 

 

 

Figure 13.  Mounding direction 

 

 

After a modular plug is inserted into the corresponding 
modular jack, lightly pull the modular cable to make sure 
the modular plug is completely connected to the modular 
jack.   

Recommended wires and cables 

For  recommended  wires  and  cables,  refer  to  the  wiring 
specifications of  

Input/output specifications

 section. 

 

Wire connection for FCU ON/OFF output, control valve 
output, and other inputs 

Quick-fit screwless terminals are provided for ON/OFF output, 
control valve output, status input, and trip alarm input.  Follow 
the procedure below for connecting these wires. (Refer to Fig. 
9.) 

1)  Remove    covers  of  the  terminals  to  which  wires  are 

connected. 

2)  Strip the 5-6 mm wire sheath to be connected to. (Scale 

is indicated on the front surface.  If a bare wire is longer 
or shorter than 5-6 mm, it may get exposed or may come 
off from the connector.)  Make sure that any  wire fiber 
goes out of the bare wire. 

3)  Insert  a  slotted  screwdriver  into  a  smaller  square  hole 

(for clamp release) on the terminal blocks located on the 
upper and the lower sides of the front surface. 
To  insert  the  screwdriver  to  deep  end  (approx.  10  mm 
deep), push and tilt it (towards the front surface) along 
the curving surface inside the square hole. 
When  the  screwdriver  is  correctly  inserted  to  the  deep 
end,  the  clamp  is  completely  released  and  the 
screwdriver remains inserted position by itself. 

Notes: 

  A slotted screwdriver with the blade 3.5 mm wide and 0.5 mm 

thick (straight type) is applicable.  A screwdriver with the blade 
end  narrower  than  the  beginning  (shaft  side)  may  not  be 
applicable. 
Applicable screwdriver (an example): 
Vessel’s Model 9900 (3 mm wide 

 100 mm long) or  

Model 910 (3 mm wide 

 75 mm long) 

  Since  the  terminal  blocks  have  the  inclined  surfaces,  required 

maintenance clearance varies depending on  the length of the 
screwdriver to be used.  Note that a long screwdriver (80 mm or 
longer) may not be usable for the Infilex FC replaced from IFC or 
Microstat  since  IFC  or  Microstat  requires  smaller  maintenance 
clearance. 

4)  After  the  a  bare  wire  is  fully  inserted,  remove  the 

screwdriver with the bare wire inserted. 

5)  Lightly  pull  the  wires  connected  to  make  sure  it  is  completely 

held by clamp. 

 

Note for connecting stripped wire of 1.8 mm

2

 or smaller 

cable 

1.8 mm

2

 or thinner cable connected to a quick-fit screwless 

terminal may cause short-circuit due to dust accumulated in 
clearance of the terminal. (See Fig. 14.) 

To prevent short-circuit, put the tubes* through the wires so 
that the wire connected terminals are covered. (See Fig. 15.)  
Tubes  are  not  supplied  with  Infilex  FC  and  commercially 
available.  See Fig. 24 for tube specifications. 

  Tubes are also available at Azbil Corporation.  

(Part No. 83167219-001, 6 pieces/set) 

 

 

 

 

 

 

 

 

 

 

 

Figure 14.  Dust accumulated in quick-fit screwless terminals 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 15.  Tubes covering quick-fit screwless terminals 

 

Connection to user terminal / temperature sensor 

Wires from user terminal / temperature sensor are connected 
to Infilex FC with modular connection.  For correctly crimping 
modular plugs on LAN cables, refer to the following section. 

Dust 

Vertical 

direction 

Horizontal 

direction 

A: Incorrect 

B: Correct 

Dust 

Tubes 

Содержание Infilex FC

Страница 1: ...entrally monitored and controlled Features Compact size Small sized body fits inside an FCU Easy installation Connectors facilitate wiring installation Two kinds of FCU control Valve ON OFF control an...

Страница 2: ...the left warns of the risk of electric shock Notifies users that specific actions are prohibited to prevent possible danger The symbol inside graphically indicates the prohibited action For example t...

Страница 3: ...MIS cannot be mixed with SMS or DSS in the same system On LS bus max 50 remote units also called sub controllers can be connected On LC bus 2 lines for 1 channel max 50 remote units also called contro...

Страница 4: ...rol type for M H N O contact potential free Contact capacity Max 3 A AC 125 V AC Max 1 5 A AC 250 V AC Min applicable load 10 mA AC Quick fit screwless terminal block JIS 4 CVV 2 0 mm 2 or equivalent...

Страница 5: ...l between mounting screws 150 120 45 189 1 interval between mounting screws 200 Dimensions Valve ON OFF control type Figure 2 Dimensions mm Model WY5305W1000 Valve proportional control type Figure 3 D...

Страница 6: ...ater valve Connect to terminals 4 and 5 Leave terminals 6 and 7 unconnected Chilled hot water valve Connect to terminals 4 and 5 Leave terminals 6 and 7 unconnected Chilled water valve hot water valve...

Страница 7: ...ter valve Note Order of valve open close operation can be set with parameters IMPORTANT If Infilex FC is used in a 24 hour operation system be sure to fully close open the valves in 0 100 position at...

Страница 8: ...des of the M4 screw hole on a screw tab Instead of cable ties two fasteners can be used to mount Infilex FC on the threaded rod Refer to Fig 8 for mounting with cable ties fasteners Infilex FC mounted...

Страница 9: ...ition any connected cable on the front surface of Infilex FC as shown in Fig 10 Precautions for Installation For Infilex FC installation tightly fix with the screws Leave clearance as shown in Figs 11...

Страница 10: ...ased and the screwdriver remains inserted position by itself Notes A slotted screwdriver with the blade 3 5 mm wide and 0 5 mm thick straight type is applicable A screwdriver with the blade end narrow...

Страница 11: ...d inner conductors into a modular plug Figure 18 LAN cable insertion into a modular plug Pin numbers of the modular plug in Fig 18 shows the pin number arrangement when you face the side with contacts...

Страница 12: ...plug Figure 23 Modular plug Part No DY7207A0100 100 pieces set Tube Prepare tubes if necessary that meets the following specifications Figure 24 Tube commercially available Precautions for use Modular...

Страница 13: ...d to another end of the devices Max 250 m Connect a terminator to any end of the devices on the bus throughout the system 1 terminator in total as shown in Fig 29 Modular branch unit Part No DY7203A00...

Страница 14: ...so that the actual measured temperature matches the preset temperature Noise control To prevent the water flushing noise the valve is completely closed when its closing position reaches the specified...

Страница 15: ...by the center unit FCU start stop operation is not available when the setback operation is active Fan speed control Fan speed is changed over L M H AUTO with a user terminal The latest changeover ope...

Страница 16: ...1 Any combination of the following valves can be used for temperature control Chilled hot water valve chilled water valve hot water valve chilled water valve hot water valve and chilled water valve ch...

Страница 17: ...it Model DY7203A0000 Neopanel with address 1 and with address 2 are required Note that two Neopanel with address 1 connected to the Infilex FC do not work Address number is indicated on the shipping c...

Страница 18: ...Properties nc25 nciNetConfig SCPTnwrkCnfg nc165 nciDevMajVer SCPTdevMajVer nc166 nciDevMinVer SCPTdevMinVer Optional Network Variables Node object Type 0 Mandatory Network Variables nviRequest SNVT_o...

Страница 19: ...OccCmd SNVT_Occupancy nv7 nviApplicMode SNVT_hvac_mode nv8 nviSetPtOffset SNVT_temp_p nv9 nvoFanSpeed SNVT_switch nv5 nvoSpaceTemp SNVT_temp_p nv15 nvoEffectSetPt SNVT_temp_p nv16 nvoOccCmd SNVT_occup...

Страница 20: ...SNVT_obj_status Object request nvoFileStat SNVT_file_status File status Configuration network variables according to LONMARK Functional Profile Node object Variable name CP type Valid range Default v...

Страница 21: ...Default value Description SB RB MT nvoHeatOutput SNVT_lev_percent 0 00 to 100 00 0 Hot water coil output nvoCoolOutput SNVT_lev_percent 0 00 to 100 00 0 Chilled water coil output nvoFanSpeed SNVT_swit...

Страница 22: ...ory read data nvoErrorState1 UNVT_error_st1 Error indication 1 error flag nvoErrorState2 UNVT_error_st2 Error indication 2 error log nvoErrorState3 UNVT_error_st2 Error indication 3 error log nvoEepro...

Страница 23: ...AB 6569 23 This blank page was added for page layout purposes...

Страница 24: ...ardous Substances Directive RoHSD EMCD EN 61326 1 Class A Table 2 for use in an industrial electromagnetic environment LVD EN 61010 1 Overvoltage category II Pollution degree 2 RoHSD EN 50581 Infilex...