User-defined network variables
User-defined input network variables
Variable name
SNVT name
Valid range
Default value
Description
SB
RB
MT
nviOutdoorTemp
SNVT_temp_p
-99.9 to 99.9
C
327.67
Outdoor temperature input
nviRainState
SNVT_switch
Wet weather indication input
nviOpeFcu1
UNVT_op_fcu1
Command (valve override
ope error indication
cancel, etc.) input
nviOperation
UNVT_operation
Command (memory read/write,
etc.) input
User-defined output network variables
Variable name
SNVT name
Valid range
Default value
Description
SB
RB
MT
nvoSetPtOffset
SNVT_temp_p
-10.00 to 10.00
C
0.00
Fine adjustment (local)
nvoLoadResetSt
SNVT_count
0 to 9
0
Control status output
nvoSpaceTemp2
SNVT_temp_p
-10.00 to 50.00
C
327.67
Analog input (temperature)
nvoSpaceRH
SNVT_lev_percent
0.000 to 100.000 %
0.000
Analog input (humidity)
nvoBattExchange
SNVT_state
Battery run-down warning
output
nvoUnitAlarm
SNVT_switch
Alarm
nvoDI
SNVT_switch
Digital input
nvoCtrlDataFcu
UNVT_dat_fcu1_2
Internal FCU control data
output
nvoIODataFcu1
UNVT_dat_fcu2_2a
Input/output data 1
nvoIODataFcu2
UNVT_dat_fcu2_2b
Input/output data 2
nvoIODataFcu
UNVT_dat_vav3_2
User terminal data
nvoControlMode
UNVT_ctrl_mode
Control mode, dummy flag,
memory read data
nvoErrorState1
UNVT_error_st1
Error indication 1
(error flag)
nvoErrorState2
UNVT_error_st2
Error indication 2
(error log)
nvoErrorState3
UNVT_error_st2
Error indication 3
(error log)
nvoEepromState
UNVT_eeprom_st
EEPROM data
nvoUpdateData
UNVT_f_update
ST_NUL
Internal data notification during
update
User-defined configuration network variables
Variable name
CP type
Valid range
Default value
Description
nciCovPara
UCPTfcuMinDelta2
(Resource file)
Load reset type + COV value
nciFcuAux
UCPTfcuAux
Auxiliary parameter
User-defined parameters
Variable name
CP type
Valid range
Default value
Description
nciSetPtHiLimit
UCPTsetPointHighLimit
0.00 to 50.00
C
30.00
Setpoint high limit
nciSetPtLoLimit
UCPTsetPointLowLimit
0.00 to 50.00
C
15.00
Setpoint low limit
nciParaFcu01
UCPTfcuCtrlType2
Operation control parameter
nciParaFcu02
UCPTfcuTempCtrl2
Temperature control parameter
nciParaFcu03
UCPTfcuDischargeAirTempCtrl2
Duct inlet temperature optimization
parameter
nciParaFcu04
UCPTfcuUnitType2
FCU parameter
nciParaFcu05
UCPTfcuFanCtrl
Fan speed automatic control
parameter
nciParaFcu06
UCPTctrlDisable
Assign/delete point parameter,
assign/delete control parameter
nciParaFcu07
UCPTfcuAI_Adjustment2
Input/output adjustment parameter
nciParaFcu08
UCPTfcuManufAdjustment2
Manufacturer adjusted parameter
nciParaFcu11
UCPTfcuMiscellaneous2
Basic parameter
nciParaFcu21
UCPTsetPointKnob2
AI processing table