Azbil Infilex FC Скачать руководство пользователя страница 16

AB-6569 

16 

 

(3/3) 

Item 

Function 

Description 

Remarks 

External contact input 
(DI) 

Alarm input 

Input value of DI (digital input) 1 is reflected in the 
alarm point.  When the contact of DI 1 is open, NML 
(0) is reflected.  When the contact of DI 1 is closed, 
ALM (1) is reflected. 

Alarm input is applicable only to Models 
WY5305W2010. 

State input 

Input value of DI (digital input) 2 is reflected in the 
general DI point.  When the contact of DI 2 is open, 
OFF (0) is reflected.  When the contact of DI 2 is 
closed, ON (1) is reflected.   

State input is applicable only to Models 
WY5305W2010. 

Interlock operation with 
DI 

FCU interlocking 
with alarm input 

When alarm input is “ALM”, FCU is turned off.  
Concurrently, FCU start/stop operation with a user 
terminal can be restricted. 

FCU automatic start/stop operation is 
not available when FCU interlocking with 
alarm input is active. 

FCU interlocking 
with status input 

When status input is “OFF”, FCU is turned off/ 
switched to setback operation.  Concurrently, FCU 
start/stop operation with a user terminal can be 
restricted. 

FCU automatic start/stop operation is 
not available when FCU interlocking with 
status input is active. 

 
Notes: 
1)  Any combination of the following valves can be used for temperature control: 

Chilled/hot water valve, chilled water valve, hot water valve, chilled water valve + hot water valve,  
and chilled water valve + chilled/hot water valve* 

  The order of valve open/close operation can be set with parameters.  

(e.g. chilled water valve 

 chilled/hot water valve OR chilled/hot water valve 

 chilled water valve) 

2)  “Water-priority” control is the method to open the valves first BEFORE the fan speed is increased.  This prevents excessive fan speed 

(airflow volume) and fan noise.   
“Fan speed-priority” control is the method to widely open the valves AFTER the fan speed is increased.  This ensures the temperature 
difference between the coil inlet and outlet, leading to the effective chiller plant control. 

3)  VWV: Variable Water Volume 

VWT: Variable Water Temperature 

4)  The latest start/stop operation with an analog user terminal may not take priority. 
5)  The latest setting operation with an analog user terminal does not take priority. 
6)  Dual setting is the method to have cooling setting and heating setting separately. 
7)  Control status is an index of FCU load.  The index is used for supply air temperature control of OAHU or VWV/VWT control. 
8)  Temperature measuring for group monitoring calculates either the average value in a group or the representative value of a group. 

 

Содержание Infilex FC

Страница 1: ...entrally monitored and controlled Features Compact size Small sized body fits inside an FCU Easy installation Connectors facilitate wiring installation Two kinds of FCU control Valve ON OFF control an...

Страница 2: ...the left warns of the risk of electric shock Notifies users that specific actions are prohibited to prevent possible danger The symbol inside graphically indicates the prohibited action For example t...

Страница 3: ...MIS cannot be mixed with SMS or DSS in the same system On LS bus max 50 remote units also called sub controllers can be connected On LC bus 2 lines for 1 channel max 50 remote units also called contro...

Страница 4: ...rol type for M H N O contact potential free Contact capacity Max 3 A AC 125 V AC Max 1 5 A AC 250 V AC Min applicable load 10 mA AC Quick fit screwless terminal block JIS 4 CVV 2 0 mm 2 or equivalent...

Страница 5: ...l between mounting screws 150 120 45 189 1 interval between mounting screws 200 Dimensions Valve ON OFF control type Figure 2 Dimensions mm Model WY5305W1000 Valve proportional control type Figure 3 D...

Страница 6: ...ater valve Connect to terminals 4 and 5 Leave terminals 6 and 7 unconnected Chilled hot water valve Connect to terminals 4 and 5 Leave terminals 6 and 7 unconnected Chilled water valve hot water valve...

Страница 7: ...ter valve Note Order of valve open close operation can be set with parameters IMPORTANT If Infilex FC is used in a 24 hour operation system be sure to fully close open the valves in 0 100 position at...

Страница 8: ...des of the M4 screw hole on a screw tab Instead of cable ties two fasteners can be used to mount Infilex FC on the threaded rod Refer to Fig 8 for mounting with cable ties fasteners Infilex FC mounted...

Страница 9: ...ition any connected cable on the front surface of Infilex FC as shown in Fig 10 Precautions for Installation For Infilex FC installation tightly fix with the screws Leave clearance as shown in Figs 11...

Страница 10: ...ased and the screwdriver remains inserted position by itself Notes A slotted screwdriver with the blade 3 5 mm wide and 0 5 mm thick straight type is applicable A screwdriver with the blade end narrow...

Страница 11: ...d inner conductors into a modular plug Figure 18 LAN cable insertion into a modular plug Pin numbers of the modular plug in Fig 18 shows the pin number arrangement when you face the side with contacts...

Страница 12: ...plug Figure 23 Modular plug Part No DY7207A0100 100 pieces set Tube Prepare tubes if necessary that meets the following specifications Figure 24 Tube commercially available Precautions for use Modular...

Страница 13: ...d to another end of the devices Max 250 m Connect a terminator to any end of the devices on the bus throughout the system 1 terminator in total as shown in Fig 29 Modular branch unit Part No DY7203A00...

Страница 14: ...so that the actual measured temperature matches the preset temperature Noise control To prevent the water flushing noise the valve is completely closed when its closing position reaches the specified...

Страница 15: ...by the center unit FCU start stop operation is not available when the setback operation is active Fan speed control Fan speed is changed over L M H AUTO with a user terminal The latest changeover ope...

Страница 16: ...1 Any combination of the following valves can be used for temperature control Chilled hot water valve chilled water valve hot water valve chilled water valve hot water valve and chilled water valve ch...

Страница 17: ...it Model DY7203A0000 Neopanel with address 1 and with address 2 are required Note that two Neopanel with address 1 connected to the Infilex FC do not work Address number is indicated on the shipping c...

Страница 18: ...Properties nc25 nciNetConfig SCPTnwrkCnfg nc165 nciDevMajVer SCPTdevMajVer nc166 nciDevMinVer SCPTdevMinVer Optional Network Variables Node object Type 0 Mandatory Network Variables nviRequest SNVT_o...

Страница 19: ...OccCmd SNVT_Occupancy nv7 nviApplicMode SNVT_hvac_mode nv8 nviSetPtOffset SNVT_temp_p nv9 nvoFanSpeed SNVT_switch nv5 nvoSpaceTemp SNVT_temp_p nv15 nvoEffectSetPt SNVT_temp_p nv16 nvoOccCmd SNVT_occup...

Страница 20: ...SNVT_obj_status Object request nvoFileStat SNVT_file_status File status Configuration network variables according to LONMARK Functional Profile Node object Variable name CP type Valid range Default v...

Страница 21: ...Default value Description SB RB MT nvoHeatOutput SNVT_lev_percent 0 00 to 100 00 0 Hot water coil output nvoCoolOutput SNVT_lev_percent 0 00 to 100 00 0 Chilled water coil output nvoFanSpeed SNVT_swit...

Страница 22: ...ory read data nvoErrorState1 UNVT_error_st1 Error indication 1 error flag nvoErrorState2 UNVT_error_st2 Error indication 2 error log nvoErrorState3 UNVT_error_st2 Error indication 3 error log nvoEepro...

Страница 23: ...AB 6569 23 This blank page was added for page layout purposes...

Страница 24: ...ardous Substances Directive RoHSD EMCD EN 61326 1 Class A Table 2 for use in an industrial electromagnetic environment LVD EN 61010 1 Overvoltage category II Pollution degree 2 RoHSD EN 50581 Infilex...

Отзывы: