Testing, start-up, diagnosis
AVENTICS
| INTERBUS | R412005655–BDL–001–AB
99
English
6.3.3
Diagnostic display on the 8-position
A24V-/0.5A-IB output module
The IB DIA and D0-D7 diagnostic LED on the 8-position output
module show the diagnostic messages listed in the table below.
This supplements the diagnostic display on the bus coupler and
more precisely defines the cause of the error. The S1/2 must be
activated with IB DIA.
6.4
Diagnostic messages
6.4.1
Diagnostic messages to the master
The status listed in Tab. 25 are not only recognized by both the
LED groups on the bus coupler or on the local bus participant's
LED but are also recognized by the control (CMD software or
PLC), if the corresponding diagnostic message on the SMD
S1 switch is activated.
Table 24:
Diagnostic display on the 8-position output module
LED
Signal
Error
Description
IB DIA Green
Green blink
1)
Green blink
2)
1)
Blinking frequency: 0.5 Hz (1 s on, 1 s off)
2)
Blinking frequency: 2 Hz (0.25 s on, 0.25 s off)
INTERBUS diagnostic display:
No errors in local bus and the bus master's bus reset is inactive.
No telegrams are being transferred.
Peripheral error (collective diagnosis, if S1/2 = ON)
DO ...
D7
Off
Red
Output is ok.
Overload or short circuit of output