APPLIANCE DESCRIPTION AND OPERATION
CH & DHW Settings / Heating Settings (Cont'd)
Demand Type
Thermostat & Outd. Curve
Thermostat & Setpoint
Constant & Outdoor Curve
Constant & Setpoint
0-10 V Modulation Signal
Demand Type
Thermostat & Outd. Curve
Thermostat & Setpoint
Constant & Outdoor Curve
Constant & Setpoint
0-10 V Modulation Signal
0 - 10V Modulation Signal
- This option allows the Prestige firing rate to be controlled by an external control
system.
Based on the control input voltage, the appliance will start to operate for heat demand. The CH temperature is
limited by the Absolute maximum temperature (87°C).
•
0 – 2V appliance is off.
•
2 – 10 V linear power increase from minimum to maximum output.
•
10 – 2 V linear power decrease from maximum to minimum output.
•
2 – 1 V appliance on minimum capacity.
•
1 - 0 V appliance off.
max
min
ou
tpu
t
0
1
2
3
4
5
6
7
8
9
10
Voltage
Press on
OK
to validate the selection.