APPLIANCE DESCRIPTION AND OPERATION
CH & DHW Settings / Heating Settings (Cont’d)
Heating Settings
CH1 Max. Setpoint
82°C
CH1 Min. Setpoint
49°C
Outdoor Curve / Coldest Day
-12°C
Outdoor Curve / Warmest Day
18°C
CH2/CV2 Circuit
Enabled
CH2 Max. Setpoint
60°C
Heating Settings
CH1 Min. Setpoint
49°C
Outdoor Curve / Coldest Day
-12°C
Outdoor Curve / Warmest Day
18°C
CH2/CV2 Circuit
Enabled
CH2 Max. Setpoint
60°C
CH2 Min. Setpoint
27°C
CH2 Min.
Setpoint
27°C
15°C
60°C
CH2 Minimum Setpoint
is the minimum setpoint for a CH2 heating call when an Out-
door Curve option is chosen in Demand Type. This setting is not applicable when a Set-
point option is chosen in Demand Type.
Press the
LEFT
or
RIGHT
buttons to adjust the CH2 Minimum Setpoint then press the
OK
button to store the setting.
Default: 27°C
Heating Settings
Outdoor Curve Coldest Day
-12°C
Outdoor Curve Warmest Day
18°C
CH2/CV2 Circuit
Enabled
CH2 Max. Setpoint
60°C
CH2 Min. Setpoint
27°C
Warm Weather Shutdown
Off
Warm Weather Shutdown
Off
Off
25°C
Warm Weather Shutdown
allows to enter an optional outdoor temperature at which to disa-
ble the central heating function. The Prestige will continue to respond to a domestic hot water
call or a 0- 10V Modulation Signal when the outdoor temperature exceeds the Warm Weather
Shutdown Temperature setting.
Press the
LEFT
or
RIGHT
buttons to adjust the Warm Weather Shutdown Temperature then
press the
OK
button to store the setting and complete the Heating setting.
The Warm Weather Shutdown icon ( ) is displayed on the home screen when the outdoor
temperature reaches the Warm Weather Shutdown Temperature.
Default: OFF
.
Heating Settings
Outdoor Curve / Warmest Day
18°C
CH2/CV2 Circuit
Enabled
CH2 Max. Setpoint
60°C
CH2 Min. Setpoint
27°C
Warm Weather Shutdown
Off
Circulation Pump Permanent
Disabled
Circulation Pump
Permanent
Disabled
Enabled
Circulation Pump Permanent
allows the central heating circulators to be con-
stantly enabled even without a central heating call. A domestic hot water call
will cause the circulators to be disabled during the domestic call as long as DHW
Priority is enabled.
Press the
UP
or
DOWN
buttons to select Enabled or Disabled then press the OK
button to store the setting.
•
Enabled
– The central heating circulators will be enabled for constant circu-
lation without a central heating call.
•
Disabled
– The central heating circulators will only be enabled during a cen-
tral heating call.
Default: Disabled