APPLIANCE DESCRIPTION AND OPERATION
CH & DHW Settings / Heating settings (Cont'd)
Demand Type
Thermostat & Outd. Curve
Thermostat & Setpoint
Constant & Outdoor Curve
Constant & Setpoint
0-10 V Modulation Signal
Demand Type
Thermostat & Outd. Curve
Thermostat & Setpoint
Constant & Outdoor Curve
Constant & Setpoint
0-10 V Modulation Signal
Thermostat & Outdoor Curve
– A central heating call from a dry contact switch will enable the Prestige
and the setpoint will vary with the outdoor temperature for central heating calls.
Press on
OK
to validate the selection.
Demand Type
Thermostat & Outd. Curve
Thermostat & Setpoint
Constant & Outdoor Curve
Constant & Setpoint
0-10 V Modulation Signal
Constant & Outd. Curve
- The Prestige will maintain setpoint and the central heating circulators will be
constantly enabled without an external call from a dry contact switch. The central heating circulators will be
disabled when the outdoor temperature exceeds the Warm Weather Shutdown Temperature setting. The
setpoint will vary with the outdoor temperature for central heating calls.
Press on
OK
to validate the selection.
Demand Type
Thermostat & Outd. Curve
Thermostat & Setpoint
Constant & Outdoor Curve
Constant & Setpoint
0-10 V Modulation Signal
Constant & Setpoint
- The Prestige will maintain setpoint and the central heating circulators will be con-
stantly enabled without an external call from a dry contact switch. The central heating circulators
will be disabled when the outdoor temperature exceeds the Warm Weather Shutdown Temperature set-
ting. The setpoint will be fixed for central heating calls.
Press on
OK
to validate the selection.