Boiler Protection
P3
DHW
P4
84°C
61°C
1
2
CH
Target = 85°C
ENTER ACCESS CODE
05[4]
CH Settings
CH & DHW Settings
Reset All Settings
Press OK
to restore factory settings,
any other button
to keep current settings.
Cascade Info.
?
Manual Operation
FAN
CH1
CH2
DHW
Released
Off
Off
Off
Select a digit using the
LEFT
and
RIGHT
buttons, and increase or
decrease the digit value using the
UP
and
DOWN
buttons.
1x
System Control - ACVMax: 660Y2800 • C
en
6
EN
FR
NL
ES
IT
DE
PL
RU
APPLIANCE DESCRIPTION AND OPERATION
INSTALLER MENU STRUCTURE
INSTALLER MENU DESCRIPTION
The installer Menu contains the following icons :
1.
CH & DHW Settings
– Allows the installer to adjust the boilers central/space heating and
domestic hot water settings for the application. Refer to "CH & DHW Settings / Heating Settings"
on page 7.
2.
Manual Operation
– The burner and circulators can be manually enabled for testing. Refer to
"Manual Operation" on page 25 .
3.
Cascade
Settings
– Allows the installer to setup, adjust and monitor the Cascade System. Refer
to "Configuration of Cascade systems - Solo (2 pumps)" on page 44.
3.
Reset All Settings
– Resets all CH, DHW, and Cascade Settings back to the factory settings (see
table below). Refer to "Reset all settings" on page 24.
CH Parameters
Factory Setting
EZ Setup
Heating Operation
Enabled
Demand
Thermostat & Outd. Curve
ü
Absolute Max CH Setpoint
87°C
CH1 Max Setpoint
82°C
ü
CH1 Min Setpoint
49°C
ü
Outdoor Curve Coldest Day
-12°C
Outdoor Curve Warmest Day
18°C
CH2/CV2 Circuit
Enabled
CH2 Max Setpoint
60°C
ü
CH2 Min Setpoint
27°C
ü
Warm Weather Shutdown
Off
ü
Circulation pump permanent
Disabled
CH Post Pump time
5 min
Freeze Protection
Enabled
Frost Protection Setpoint
-30°C
Parallel Shift Value
0°C
CH Call Blocking
2 min
5.
Home
- to go back to the home page.
6. Back - to go back to the previous screen.
CH & DHW Settings
Reset All Settings
Cascade Information
Manual Operation