- 47 -
(2)Basic faults diagnose process of 18000BTU~24000BTU
1. The Foremost Inspecting Items
⑴
The input voltage must be 10% tolerance of the rated Voltage. If it is not the case,
the air-conditioner will probably not work normally.
⑵
Check the connecting cord between indoor unit and outdoor unit to see if it is properly
connected. The connecting must be done according to the wiring diagram, please also notice
that even different models may have the connecting cord of the same specification.
Please check if the marks at the connecting terminal and the marks on the cord can match,
otherwise, the air-conditioner will not work normally.
⑶
If the following phenomena are found, the problem is not from the air-conditioner itself.
NO. Problems
Causes
1
The motor is heard operating
but the air-conditioner dose not
work when the indoor unit is
powered on
Since the air-conditioner is powered
on, it will come to working condition as long
as you press the ON/OFF button of the
remote control and the signal is well
received.
2
The compressor stops running
but the indoor fan motor keeps
working when it is at cooling mode
with the indoor temperature higher
than set temperature.
If you turn off the air-conditioner and
restart it immediately, it will return to normal
in 3 minutes, after that, the air-conditioner
will automatically adjust the indoor fan
speed to what you set.
3
The compressor works
discontinuously at
dehumidifying
mode.
The air-conditioner will automatically
control the working of the compressor
according to the inside temperature
4
The air-conditioner does not
work while the LED display is on.
The TIMER is set with the
air-conditioner; it will be in hold on
condition. If the TIMER setting is cancelled,
the air-conditioner will return to normal
working condition.
5
The compressor works
discontinuously at cooling and
dehumidifying mode, and the
indoor fan motor slows down.
The compressor stops internally or the
fan motor slows down to prevent the indoor
heat exchanger from being frozen.
2. No Power Display
⑴
Items
①
Check if the input voltage is correct?
②
Check if the AC power supply connecting is correct?
③
Check if the output voltage of the manostat L7805 (IC2)is correct?
⑵
Trouble shooting procedure
Содержание ASW-H09A4/EAR1-dw
Страница 1: ...For model ASW H09A4 EAR1 dw ASW H12B4 EAR1 dw ASW H18B4 EAR1 dw ASW H24B4 EAR1 dw ...
Страница 6: ... 4 Remote Controller Instructions ...
Страница 7: ... 5 ...
Страница 8: ... 6 ...
Страница 9: ... 7 ...
Страница 10: ... 8 ...
Страница 11: ... 9 ...
Страница 12: ... 10 ...
Страница 13: ... 11 ...
Страница 14: ... 12 ...
Страница 20: ... 18 2 18000 BTU 1 Indoor Unit Cooling Only Cooling Heating 2 Outdoor Unit Cooling Only Cooling Heating ...
Страница 21: ... 19 3 24000 BTU 1 Indoor Unit Cooling Only Cooling Heating 2 Outdoor Unit Cooling Only Cooling Heating ...
Страница 47: ... 45 7 Remote Control Can Not Work Trouble shooting procedure 8 The Failure Analysis of the Main Parts ...
Страница 48: ... 46 ...
Страница 53: ... 51 7 Remote Control Can Not Work Trouble shooting procedure 8 The Failure Analysis of the Main Parts ...
Страница 68: ... 68 Exploded Pictures 1 Indoor unit exploded picture 7K 9K 12K BTU E Series ...
Страница 70: ... 70 2 Outdoor unit exploded picture 7K 9K 12K BTU E Series ...
Страница 72: ... 72 3 Indoor unit exploded picture 18K 24K BTU E Series ...
Страница 74: ... 74 4 Outdoor unit exploded picture 18K 24K BTU E Series ...
Страница 76: ......