- 24 -
⑧
The four-way valve starts immediately once being electrified.10 seconds later the
compressor starts; Under the compressor opening condition, the four-way valve shuts off after
2 minutes and 50 seconds delay protection when turn off or switch the controller; The
four-way valve turns off immediately after turning off the controller when the compressor is off;
⑨
Anti cold-wind and Residual-heat Removing function:
TE controls the wind speed of the indoor fan, and the specific conditions are as below:
The anti cold-wind status when the compressor runs:
a) When TE in rise status and at the moment of TE
<
TE1
,
the indoor fan turns off
;
TE2
≤
TE
<
TE3
,
the indoor fan blows the breeze; TE3
≤
TE
<
TE4
,
the indoor fan blows the mute wind;
TE
≥
TE4
,
the indoor fan blows the set wind speed;
b)When TE in fall status and at the moment of TE
>
TE5
,
the indoor fan blows the set wind
speed; TE6
<
TE
≤
TE5
,
the indoor fan blows the mute wind
;
TE7
<
TE
≤
TE6
,
the indoor fan
blows the breeze
;
TE
≤
TE7
,
the indoor fan turns off.
The anti cold-wind status when the compressor stops working:
a
)
Monitoring. T
E>
30
℃,
the indoor fan blows breeze for 30 s , then indoor fan turns off
;
once
there is T
E≤
30
℃
in this 30 s
,
indoor fan turns off
;
b
)
Monitoring. T
E≤
30
℃,
indoor fan turns off
;
The residual-heat Removing function
:
When TE
>
TE8
,
the indoor fan runs in breeze
,
if
≤
TE8
,
the indoor fan stops working, and the
time in removing residual heat
≤
10seconds
,
Within the 10 seconds of residual heat removing,
Содержание ASW-H09A4/EAR1-dw
Страница 1: ...For model ASW H09A4 EAR1 dw ASW H12B4 EAR1 dw ASW H18B4 EAR1 dw ASW H24B4 EAR1 dw ...
Страница 6: ... 4 Remote Controller Instructions ...
Страница 7: ... 5 ...
Страница 8: ... 6 ...
Страница 9: ... 7 ...
Страница 10: ... 8 ...
Страница 11: ... 9 ...
Страница 12: ... 10 ...
Страница 13: ... 11 ...
Страница 14: ... 12 ...
Страница 20: ... 18 2 18000 BTU 1 Indoor Unit Cooling Only Cooling Heating 2 Outdoor Unit Cooling Only Cooling Heating ...
Страница 21: ... 19 3 24000 BTU 1 Indoor Unit Cooling Only Cooling Heating 2 Outdoor Unit Cooling Only Cooling Heating ...
Страница 47: ... 45 7 Remote Control Can Not Work Trouble shooting procedure 8 The Failure Analysis of the Main Parts ...
Страница 48: ... 46 ...
Страница 53: ... 51 7 Remote Control Can Not Work Trouble shooting procedure 8 The Failure Analysis of the Main Parts ...
Страница 68: ... 68 Exploded Pictures 1 Indoor unit exploded picture 7K 9K 12K BTU E Series ...
Страница 70: ... 70 2 Outdoor unit exploded picture 7K 9K 12K BTU E Series ...
Страница 72: ... 72 3 Indoor unit exploded picture 18K 24K BTU E Series ...
Страница 74: ... 74 4 Outdoor unit exploded picture 18K 24K BTU E Series ...
Страница 76: ......