MODBUS R
T
U
D0–DCM with
5–8
D0–DCM Using MODBUS
DL05/06 Data Communications Module, 1st Edition, 08/05
Find the MODBUS address for User V
location V2100.
1.
Find V memory in the table.
2.
Convert V2100 into decimal (1088).
3.
Add the MODBUS starting address for the
mode (40001).
PLC Address (Dec.) + Mode Address
V2100 = 1088 decimal
1088 + 40001 = 41089
Find the MODBUS address for output Y20.
1.
Find Y outputs in the table.
2.
Convert Y20 into decimal (16).
3.
Add the starting address for the range
(2048).
4.
Add the MODBUS address for the mode
(1).
PLC Addr. (Dec) + Start A Mode
Y20 = 16 decimal
16 + 2048 + 1 = 2065
Find the MODBUS address for Control Relay
C54.
1.
Find Control Relays in the table.
2.
Convert C54 into decimal (44).
3.
Add the starting address for the range
(3072).
4.
Add the MODBUS address for the mode
(1).
PLC Addr. (Dec) + Start A Mode
C54 = 44 decimal
44 + 3072 + 1 = 3117
Example 1: V2100
Example 2: Y20
Example 3: C54