Your PC’s Windows calculator can be used for number conversions (i.e. decimal to octal). The
Windows calculator must be in Calculator>View>Scientific mode to enable number conversions
capability.
Find the PLC address to use to target MODBUS
address 41025 in a server device.
1.
Subtract the begining of the MODBUS word
address range (40001) from the desired
MODBUS address to target.
2.
Convert decimal result into octal.
3.
Add octal result to begining PLC range
(Input, Output or Word).
2. 1024 decimal = 2000 octal
1. 41025 – 40001 = 1024 decimal
3. V0 (octal) + 2000 (octal) = V2000 octal
Find the PLC address to use to target MODBUS
address 12060 in a server device.
1.
Subtract the begining of the MODBUS Input
address range (12049) from the desired
MODBUS address to target.
2.
Convert decimal result into octal.
3.
Add octal result to begining PLC range
(Input, Output or Word).
2. 11 decimal = 13 octal
1. 12060 – 12049 = 11 decimal
3 X0 (octal) + 13 (octal) = X13 octal
Example 1:
Calculating Word
PLC Address
Example 2:
Calculating Discrete
Input PLC Address
Содержание D0-DCM
Страница 1: ...D0 DCM Data Communications Module Manual Number D0 DCM M...
Страница 8: ......
Страница 9: ...1 1 Introduction In This Chapter Manual Overview D0 DCM Hardware Features D0 DCM Applications...
Страница 24: ......
Страница 56: ......
Страница 57: ...1 5 D0 DCM Using MODBUSr RTU In This Chapter Network Slave Operation Network Master Operation...