5–2
D0–DCM Using MODBUS
DL05/06 Data Communications Module, 1st Edition, 08/05
Network Slave Operation
This section describes how a MODBUS RTU master on a network can communicate
with a D0–DCM using the MODBUS RTU protocol. A network master must send a
MODBUS function code and MODBUS address to specify a PLC memory location in
the DL05/06 CPU. No CPU ladder logic is required to support MODBUS slave
operation.
The D0–DCM supports the following MODBUS function codes when acting as a
MODBUS slave.
MODBUS
Function Code
Function
DL05/06
Data Types Available
01
Read Output Table
Y, C, T, CT
02
Read Input Table
X, SP
03
Read Holding Registers (when addressing
mode is 584/984, this function is used to ac-
cess analog output registers)
V
04
Read Input Registers (when addressing mode
is 584/984, this function is used to access
analog input registers)
V
05
Force Single Output
Y, C, T, CT
06
Preset Single Registers
V
08
Loop back / Maintenance
15
Force Multiple Outputs
Y, C, T, CT
16
Preset Multiple Registers
V
There are typically two ways that most MODBUS addressing conventions allow you
to specify a PLC memory location. These are:
•
By specifying the MODBUS data type and address
•
By specifying a MODBUS address only.
MODBUS Function
Codes Supported
Determining the
MODBUS Address
Содержание D0-DCM
Страница 1: ...D0 DCM Data Communications Module Manual Number D0 DCM M...
Страница 8: ......
Страница 9: ...1 1 Introduction In This Chapter Manual Overview D0 DCM Hardware Features D0 DCM Applications...
Страница 24: ......
Страница 56: ......
Страница 57: ...1 5 D0 DCM Using MODBUSr RTU In This Chapter Network Slave Operation Network Master Operation...