DCM Port
Configuration
Installation and
Safety Guidelines
3–7
D0–DCM Setup
DL05/06 Data Communications Module, 1st Edition, 08/05
Port 2: Protocol
Protocol
Bit 7–4
(Hex)
Bit 7
Bit 6
Bit 5
Bit 4
K–Sequence
8
1
0
0
0
DirectNet
4
0
1
0
0
MODBUS RTU
2
0
0
1
0
Non–Sequence
1
0
0
0
1
K–Seq / D–Net
/MODBUS RTU
E
1
1
1
0
Port 2: Communication Time–out (ms)
K–Seq, D–Net,
MODBUS RTU
Non–Sequence
Protocol
Bit 10
Bit 9
Bit 8
Base Time x 1
0
0
0
0
Base Time x 1.2
2
0
0
1
Base Time x 1.5
5
0
1
0
Base Time x 2
10
0
1
1
Base Time x 5
20
1
0
0
Base Time x 10
50
1
0
1
Base Time x 20
100
1
1
0
Base Time x 50
500
1
1
1
Port 2: Echo Suppression
Mode
Bit 11
RS–422/485: 4–wire
RS–232
0
RS–485: 2–wire
1
Port 2: RTS On Delay
Time (ms)
Bit 14
Bit 13
Bit 12
0
0
0
0
2
0
0
1
5
0
1
0
10
0
1
1
20
1
0
0
50
1
0
1
100
1
1
0
500
1
1
1