User Application
Guidelines
RLL
Programming
for Communications
4–7
RLL Programming for Communications
DL05/06 Data Communications Module, 1st Edition, 08/05
You can address the different data types by any available convention shown in the
tables that follow. The largest block of data that can be sent in a single Read or Write
operation is 128 bytes. The smallest block of data is one byte for Bit Memory types
and two bytes, or one word for Word Memory types. The octal numbering system is
used for all addresses in these tables.
DL05 CPU
Data Types
Bit Memory
Word Memory
Alias
Timer Current Values
None
V0 – V177
TA0 – TA177
Counter Current Values
None
V1000 – V1177
CTA0 – CTA177
User Data Words
None
V1200 – V7377
None
Input Points
X0 – X377
V40400 – V40417
VX0 – VX360
Output Points
Y0 – Y377
V40500 – V40517
VY0 – VY360
Control Relays
C0 – C777
V40600 – V40677
VC0 – VC760
Special Relays
SP0 – SP777
V41200 – V41237
VSP0 – VSP760
Timer Status Bits
T0 – T177
V41100 – V41107
VT0 – VT160
Counter Status Bits
CT0 – CT177
V41140 – V41147
VCT0 – VCT160
Stages
S0 – S377
V41000 – V41017
VS0 – VS360
DL06 CPU
Data Types
Bit Memory
Word Memory
Alias
Timer Current Values
None
V0 – V377
TA0 – TA177
Counter Current Values
None
V1000 – V1177
CTA0 – CTA177
User Data Words
None
V400 – V677
V1200 – V7377
V10000 – V17777
None
Input Points
X0 – X777
V40400 – V40437
VX0 – VX760
Output Points
Y0 – Y777
V40500 – V40537
VY0 – VY760
Control Relays
C0 – C1777
V40600 – V40677
VC0 – VC1760
Special Relays
SP0 – SP777
V41200 – V41237
VSP0 – VSP760
Timer Status Bits
T0 – T377
V41100 – V41117
VT0 – VT160
Counter Status Bits
CT0 – CT177
V41140 – V41147
VCT0 – VCT160
Stages
S0 – S1777
V41000 – V41077
VS0 – VS1760
Remote I/O
GX0 – GX3777
GY0 – GY3777
V40000 – V40177
V40200 – V40377
VGX0 – VGX3760
VGY0 – VGY3760
DL05 CPU
DirectSOFT32
is Flexible
DL06 CPU
Содержание D0-DCM
Страница 1: ...D0 DCM Data Communications Module Manual Number D0 DCM M...
Страница 8: ......
Страница 9: ...1 1 Introduction In This Chapter Manual Overview D0 DCM Hardware Features D0 DCM Applications...
Страница 24: ......
Страница 56: ......
Страница 57: ...1 5 D0 DCM Using MODBUSr RTU In This Chapter Network Slave Operation Network Master Operation...