DCM Port
Configuration
Installation and
Safety Guidelines
3–2
D0–DCM Setup
DL05/06 Data Communications Module, 1st Edition, 08/05
DCM Port Configuration Registers
The table below lists the special V-memory locations used by the DL05 and DL06
PLCs for the D0–DCM module. The following pages define each registers function.
Module Configuration
Parameters
DL05 and DL06 Option Slot
Parameters
Word
Offset
DL05
DL06
Slot 1
DL06
Slot 2
DL06
Slot 3
DL06
Slot 4
A
Port 1–Transmit Mode
(ASCII/Hex), Protocol
+0000
V7700
V700
V710
V720
V730
B
Port 1–Station Address,
Baud Rate , Parity
+0001
V7701
V701
V711
V721
V731
C
Port 2–RTS On/Off Delay,
Transmit Mode (ASCII/
Hex), Protocol, Comm
Time–out, RS–485 Mode
Select
+0002
V7702
V702
V712
V722
V732
D
Port 2–Station Address,
Baud Rate, Data Bit , Stop
Bit , Parity
+0003
V7703
V703
V713
V723
V733
E
Port 2–Character Time–
out
+0006
V7706
V706
V716
V726
V736
F
Port1/Port 2 – Setup
Completion Code
+0007
V7707
V707
V717
V727
V737
G
Port 1/Port 2–
Reset Time–out
V7730
V7730
V7731
V7732
V7733
On power up, the DCM will write the necessary data to the V–memory configuration
registers to result with the following default port communications parameters. If you
need to change any of the default settings, you must use ladder logic code to update
the appropriate configuration register.
Default Settings
Parameter
Port 1
Port 2
Baud Rate
9600bps
19200bps
Parity
Odd
Protocol
K–Sequence/DirectNet/MODBUS
(auto–detect)
Station Address
1
Data Bits
8 (fixed)
8
Stop Bits
1 (fixed)
1
Module
Configuration
Registers
Comm Port
Default
Configuration
Parameters
Содержание D0-DCM
Страница 1: ...D0 DCM Data Communications Module Manual Number D0 DCM M...
Страница 8: ......
Страница 9: ...1 1 Introduction In This Chapter Manual Overview D0 DCM Hardware Features D0 DCM Applications...
Страница 24: ......
Страница 56: ......
Страница 57: ...1 5 D0 DCM Using MODBUSr RTU In This Chapter Network Slave Operation Network Master Operation...